D-500 MK2 User Manual Firmware V-6.3
- 35 -
Measurement method:
True RMS
Sampling rate:
8000 Hz
Harmonic analysis:
up to 31th harmonic
Supported topologies:
3 ph 4 wires star, 3 ph 4 wires delta,
3 ph 3 wires delta
3 ph 3 wires delta L1-L2
3 ph 3 wires delta L2-L3
2ph 3 wires L1-L2
2ph 3 wires L1-L3
1 ph 2 wires
CT secondary rating:
5A
Measurement range:
5/5 to 5000/5A minimum
Input impedance:
15 milliohm
Burden:
0.375W
Maximum continuous
current:
6A
Measurement range:
0.1 to 7.5A
Common mode offset:
Max 5VAC between BAT- and any CT terminal.
Display resolution:
1A
Accuracy:
0.5% + 1 digit @ 5A (± 4.5A @ 5/500A full range)
4.3.2. 3 X MAINS CT INPUTS SLOT
Содержание D-500 MK2
Страница 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK2 User Manual Firmware V 6 3 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK2 User Manual Firmware V 6 3 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK2 User Manual Firmware V 6 3 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK2 User Manual Firmware V 6 3 72 ...