D-500 MK2 User Manual Firmware V-6.3
- 134 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
System Reserve Power
kW
0
65000
20
The master keeps this amount of extra
power available during whole operation
under load as a safety against a sudden
load surge.
Load Management
Method
-
0
1
0
0:
Equal Aging
1:
Smart
Dead Busbar Limit for
Multi Genset System
VAC
0
300
50
This parameter defines the minimum
voltage for the detection of a live busbar.
Governor Control Enable
-
0
1
1
0:
Governor control disabled.
1:
Governor control enabled.
Governor Output
Reverse Polarity
-
0
1
0
0:
Governor control normal polarity
(speed increases with voltage increase).
1:
Governor control reverse polarity
(speed decreases with voltage increase).
Governor Output Low
Lim
%
0
100.0
0.0
This parameter defines governor control
output low limit. Limits from 0V to 10V
can be set by this parameter
Governor Output Gain
Lim
%
0
100.0
100.0
This parameter defines governor control
output gain.
Governor Output Rest
Point
%
0
100.0
50.0
This is the rest value of the governor
control output at no load.
Governor Droop Enable
-
0
1
0
0:
Governor droop mode disabled.
1:
Governor droop mode enabled.
Governor Output Droop
%
0
100.0
0
The controller will inject this quantity of
droop at the genset rpm at 100% active
power load.
AVR Control Enable
-
0
1
1
0:
AVR control disabled.
1.
AVR control enabled.
AVR Reverse Polarity
-
0
1
1
0:
AVR control normal polarity (voltage
increases with value increase).
1:
AVR control reverse polarity (voltage
decreases with value increase).
AVR Output Low Limit
%
0
100.0
0.0
This parameter defines AVR output low
limit. Limits from -3.0V to +3.0V can be
set by this parameter
AVR Output High Limit
%
0
100.0
100.0
This parameter defines AVR output high
limit. Limits from -3.0V to +3.0V can be
set by this parameter
AVR Output Rest Point
%
0
100.0
50.0
This is the rest value of the AVR control
output at no load.
AVR Droop Enable
-
0
1
0
0:
AVR droop mode disabled.
1:
AVR droop mode enabled.
AVR Output Droop
%
0
100.0
0.0
The controller will inject this quantity of
droop at the genset voltage at 100%
reactive power load.
Excitation Loss Alarm
Level
-
0
3
2
0:
not used
1:
engine shutdown
2:
load-dump alarm
3:
warning
No Break Transfer
Enable
-
0
1
0
0:
only interrupted transfer enabled
1:
no break transfer enabled
Synchronization Fail
Timeout
sec
0
600
30
If the phase and voltage synchronization
is not successful before the expiration of
this timer, then a Synchronization Fail
warning is given and the transfer will be
performed with interruption.
Содержание D-500 MK2
Страница 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK2 User Manual Firmware V 6 3 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK2 User Manual Firmware V 6 3 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK2 User Manual Firmware V 6 3 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK2 User Manual Firmware V 6 3 72 ...