System Installation and Configuration
96-30051-001 Rev. D3
DDN SFA12K (SFA OS 2.3.1) Hardware Installation & Configuration Guide | 24
2.
Turn on the ATSs by turning on the PDUs.
3.
Ensure the ATS digital display shows “0”, indicating that it is ready.
4.
Connect the Ethernet RJ-45 port on the ATS front panel directly to the network
interface of the computer that will be used to configure the ATS
5.
Configure the IP address of the setup computer’s Ethernet port to an address in the
same subnet as the ATS you are connecting to (see
). Refer to your operating
system reference documentation on how to configure the Ethernet port.
6.
Open a browser to access the ATS by its IP address as shown in Table
above.
Use Mozilla Firefox version 1.x or higher. Use Microsoft Internet Explorer (IE) 5.5 or
higher on Windows operating systems.
7.
Enter the user name and password. The default administrator user name is
apc
and
password is
apc
. Note that entries are case sensitive.
If you are unable to connect to the ATS Web interface, check the Ethernet cabling and retry.
8.2
Configure the Parameters
You must configure these parameters according to the nominal AC voltage at your site.
1.
Log in to the ATS’s Web interface as described in Section
above.
2.
Determine the Source A and Source B voltages
:
❖
Go to
Unit
tab
❖
Select
Measurements
If the two AC Line voltages are within 10 volts, then compute their average and
proceed; otherwise, please contact DDN Support.
Table 2. Network Interface Settings for ATS Units
ATS 0
ATS 1
IP Address
10.0.0.3
10.0.1.3
Subnet Mask
255.255.255.0
255.255.255.0
Gateway
10.0.0.0
10.0.1.0
Configuring Computer IP Address
10.0.0.4
10.0.1.4
Figure 15. ATS Front Panel
Ethernet port
Displays 0 when
bootup is complete