background image

System Installation and Configuration

96-30051-001 Rev. D3

DDN SFA12K (SFA OS 2.3.1) Hardware Installation & Configuration Guide | 20

Controller 0

Controller 1

Figure 11.  Connecting SFA12KXE/12K-20E Controllers to ATSs and BBU Model 1550

Controller 0’s BBU

Controller 1’s BBU

Controller 0’s ATS

Controller 1’s ATS

Model 1550

Model 1550

InfiniBand cable

AC power cable

USB cable

Содержание SFA12Ki

Страница 1: ...Hardware Installation Configuration Guide SFA12Ki SFA12KX SFA12K 40 SFA12K 20 SFA12KXE SFA12K 20E SFA12K Series SFA OS Version 2 3 1 96 30051 001 Revision D3...

Страница 2: ...ion the implied warranties of merchantability and fitness for a particular purpose of any products or software DataDirect Networks does not warrant guarantee or make any representations regarding the...

Страница 3: ...noted SFA12K 20 the block storage appliance SFA12KX 12K 40 the high performance block storage appliance twice the disk bandwidth performance of SFA12K 20 SFA12KXi the ultra high IOPS and bandwidth blo...

Страница 4: ...face 23 8 2 Configure the Parameters 24 8 3 Other Recommended Configurations 26 8 4 Reconnect ATS 27 9 Powering On the System 28 9 1 Powering On using the Controller Power Button 30 10 Serial Interfac...

Страница 5: ...ks 39 19 3 Create and Assign Spare Pools 40 20 SFA12K Host Connections 41 21 Present Virtual Disks to External Hosts 41 21 1 Create a Host 41 21 2 Map Hosts to Discovered Initiators 42 21 3 Create the...

Страница 6: ...ge Parameters 25 Figure 18 Select Preferred Source 26 Figure 19 ATS Front Panel 26 Figure 20 Reconnect Power Cables from ATS with BBU Model 5P1550GR 27 Figure 21 Reconnect Power Cables to ATS with BBU...

Страница 7: ...Secure Front of Rail to Rack 53 Figure 68 Remove BBU Front Covers 54 Figure 69 Connect BBU Battery 54 Figure 70 ATS Rackmount Kit 55 Figure 71 BBU Alignment Washer and ATS Pan Head Screw 55 Figure 72...

Страница 8: ...with 1 x SS7000 Enclosure 87 Figure 104 SFA12KXE 12K 20E Configuration with 2 x SS7000 Enclosures 88 Figure 105 SFA12KXE 12K 20E Configuration with 3 x SS7000 Enclosures 89 Figure 106 SFA12KXE 12K 20E...

Страница 9: ...For block storage configurations create storage pools virtual disks spare pools and presentations Sections 16 to 21 2 Unpacking the System If your system is already installed in the racks refer to th...

Страница 10: ...Installation and Service Guide for additional information on safety requirements 3 Rack Installation Refer to Appendix A for instructions on how to install a SFA12K controller BBU and ATS into a rack...

Страница 11: ...ong the disk enclosures Always fill the rows from front to back also see Section 5 1 for blank module requirements Place disks with similar rotational speed in the same row If a mixture of disk techno...

Страница 12: ...your system is already installed in the racks there are four shipping screws installed on the front panel of each disk enclosure to secure them for transit These screws must be removed or loosened be...

Страница 13: ...pulling until the enclosure locks and you hear a clicking sound 2 Open the enclosure covers 3 Release the handle on the disk module 4 Insert the module into a disk bay Cam the disk module home The cam...

Страница 14: ...n the controller and its BBU as shown 4 For each ATS connect the power cable to its BBU as shown 5 Attach a power cord retainer included in the accessory kit to each of the power supply on the control...

Страница 15: ...are Installation Configuration Guide 15 Controller 1 s BBU Model 5P1550GR Controller 0 Controller 0 s BBU Controller 1 Controller 0 s ATS Controller 1 s ATS Figure 6 Connecting SFA12K 20 Controllers t...

Страница 16: ...Hardware Installation Configuration Guide 16 Controller 0 Figure 7 Connecting SFA12K 20 Controllers to ATSs and BBU Model 1550 Controller 0 s BBU Controller 1 s BBU Controller 0 s ATS Controller 1 s...

Страница 17: ...nstallation Configuration Guide 17 Controller 1 s BBU Model 5P1550GR Controller 0 s BBU Model 5P1550GR Controller 1 Controller 0 Controller 0 s ATS Controller 1 s ATS Figure 8 Connecting SFA12KXi 12KX...

Страница 18: ...ware Installation Configuration Guide 18 Controller 1 Figure 9 Connecting SFA12KXi 12KX 12K 40 Controllers to ATS and BBU Model 1550 Controller 0 Controller 0 s BBU Controller 1 s BBU Controller 0 s A...

Страница 19: ...Installation Configuration Guide 19 Controller 1 s BBU Model 5P1550GR Controller 0 s BBU Model 5P1550GR Controller 1 Figure 10 Connecting SFA12KXE 12K 20E Controllers to ATSs and BBU Model 5P1500GR Co...

Страница 20: ...dware Installation Configuration Guide 20 Controller 0 Controller 1 Figure 11 Connecting SFA12KXE 12K 20E Controllers to ATSs and BBU Model 1550 Controller 0 s BBU Controller 1 s BBU Controller 0 s AT...

Страница 21: ...ctors to the PDUs It is recommended to connect the ATS Source A to the PDUs on the left side when viewed from the back of the rack and connect Source B to the PDUs on the right side 3 Connect the disk...

Страница 22: ...N SFA12K SFA OS 2 3 1 Hardware Installation Configuration Guide 22 Figure 12 Example of PDU Wiring in Rack Rear View ATS BBU Controller 0 BBU ATS Controller 1 Disk Enclosure Disk Enclosure Disk Enclos...

Страница 23: ...rent network interface settings on the ATS NOTE It is recommended that the ATS remains disconnected from any management networks after initial setup unless you plan on monitoring it with event notific...

Страница 24: ...ernet Explorer IE 5 5 or higher on Windows operating systems 7 Enter the user name and password The default administrator user name is apc and password is apc Note that entries are case sensitive If y...

Страница 25: ...ed For example using the data in Figure 16 Source A Voltage 249 Source B Voltage 240 Average AC Line voltage 249 240 2 244 5 Nominal AC line voltage 240 because that is the closest number to 244 5 fro...

Страница 26: ...referred source Go to Unit tab Select Configuration source Figure 18 In the Preferred Source field select None Click Apply to save the changes 6 Verify that the Input A and B LEDs are both illuminated...

Страница 27: ...the controllers and BBUs 1 Turn off the ATSs by turning off the PDUs 2 Reconnect the power cords between the units as shown in Figure 20 and Figure 21 Figure 20 Reconnect Power Cables from ATS with BB...

Страница 28: ...ATSs Figure 22 Verify that the unit displays 0 on the front panel indicating that it is ready Verify that both Input A and B LEDs are ON indicating that the ATS is operating with full source redundan...

Страница 29: ...ON check the power input to the BBU Verify that both Load Segment 1 and Load Segment 2 LEDs turn ON after 13 seconds 7 Turn on both controllers Remove the controller front bezel Press the power button...

Страница 30: ...rnet connection it is first necessary to configure the network settings on each controller This can only be done using the serial interface as described in Section 11 The RS 232 console can also be us...

Страница 31: ...hernet interfaces on the SFA12KXE 12K 20E controller support SR IOV Single Root I O Virtualization which allows you to bind a virtual function interface associated with the SFA controller s own Ethern...

Страница 32: ...255 255 240 0 inet6 addr fe80 201 ffff fe0a 4f5 64 Scope Link UP BROADCAST RUNNING MULTICAST MTU 1500 Metric 1 RX packets 451807 errors 0 dropped 1039 overruns 0 frame 0 TX packets 51763 errors 0 dro...

Страница 33: ...see an alert message below the Health Indicator which shows that manual intervention is required for both controllers For E platforms with storage pre configured the Health indicator should be green...

Страница 34: ...e Then enter the MARK SUBSYSTEM TEXT command For example MARK SUBSYSTEM TEXT MAIN CTLR 0 BBU BAT SET TO 2014 09 13 Mark the log for both BBUs 14 Subsystem Configuration 14 1 Verify Physical Disk Statu...

Страница 35: ...s in any order Each controller name needs to be unique in the subsystem 3 Click Update to save the changes 15 Accessing the Virtual Machines on E Platforms The SFA12KXE 12K 20E initial subsystem confi...

Страница 36: ...n Figure 36 Host Ports on SFA12K 20 Controller InfiniBand Option Figure 37 Host Ports on SFA12K 20 Controller Dual Port FC 16 Option 0 3 2 1 1 0 3 2 Figure 33 Host Ports on SFA12KXi 12KX 12K 40 Contro...

Страница 37: ...in the SED Default Password document attached to the enclosure covers Please refer to Section 20 and Section 21 for information on connecting your hosts and configuring presentations 18 Encryption Po...

Страница 38: ...rtual disk of 10 GiB Figure 38 illustrates the disk channels that are served by RP0 and RP1 on the SFA12K controllers 19 1 Create Storage Pools NOTE It is NOT recommended to configure storage pools wi...

Страница 39: ...ded that you select the DirectProtect method at the time of pool creation Also refer to the SFA OS User Guide for additional information on all the pool attributes which may also be changed later Sele...

Страница 40: ...l contains physical disks that can be used as spare disks in one or more storage pools Up to 32 spare pools are supported Spare pools can be shared by storage pools or dedicated to a particular storag...

Страница 41: ...Section 16 for host port locations 21 Present Virtual Disks to External Hosts NOTE For E platforms the feature to present virtual disks to external hosts is not applicable Virtual disks are only prese...

Страница 42: ...splays Figure 45 2 Select the initiator 3 Select the corresponding hosts 4 Click Import Initiator Success or error message displays 5 Repeat the above steps to create other host to initiator mappings...

Страница 43: ...y pathed through and if the host connection is lost access to that VD is also lost LUN LUN that the virtual disk will show to the host Channels from which host port the host will see the virtual disk...

Страница 44: ...ypes of controller rail The standard rail which ships with the product is designed for use with racks with vertical post separation distance of 26 75 and greater Figure 47 An optional short rail kit i...

Страница 45: ...flanges to the two sides of the controllers using six screws Figure 50 CAUTION The main purpose of the chassis handles is for rackmount use only Do NOT lift carry or transport the controller by the h...

Страница 46: ...ack Installation 96 30051 001 Rev D3 DDN SFA12K SFA OS 2 3 1 Hardware Installation Configuration Guide 46 Figure 51 Release Inner Rail Pull Inner Rail Out Locking Tab Outer Rail Middle Rail Inner Rail...

Страница 47: ...ner rail with the hooks on the chassis Slide the inner rail forward until it clicks into the locked position NOTE The left and right rails differ from each other Do not exchange the inner rails 4 Use...

Страница 48: ...iddle rail back into the outer rail Figure 54 6 Hang the hooks of the rail on the rack holes Figure 55 Round hole adapters are available for use on racks with round screw holes Optional Secure rail wi...

Страница 49: ...nal Secure with two screws Similarly attach the other rail to rack 8 Pull the middle rail out of the front of the outer rail and make sure that the ball bearing shuttle is locked at the front of the m...

Страница 50: ...n both sides of the chassis until it clicks into the fully extended position Figure 57 NOTE Due to the weight of the controller a minimum of two people is required for safe installation of the chassis...

Страница 51: ...e front bezel Figure 60 The bezel uses ball stud and clip fasteners Align the clips at each corner of the bezel Figure 61 with the ball studs on the flanges Figure 62 Push the bezel in until all four...

Страница 52: ...washers Figure 63 Note that the power cord retainers are not used with the SFA12K Remote Power Connector Ensure that the remote power connector is securely attached to the back panel of the BBU as sho...

Страница 53: ...th of your rack Figure 66 Use two screws and washers to attach the rear end Use one screw and washer at the bottom to attach the front 2 Attach the two mounting brackets to the two sides of the BBU us...

Страница 54: ...nect the battery as shown in Section A 2 3 A 2 3 Connect Battery on Model 5P1550GR The BBUs are shipped with the batteries disconnected Follow these steps to connect the batteries 1 Remove the front c...

Страница 55: ...Remove the four screws and alignment washers that hold the BBU slides to the rack s rear vertical mounting rails Keep the four alignment washers from the BBU but discard the BBU mounting screws The p...

Страница 56: ...the ATS to the two brackets using the four flat head screws two screws on each side as shown in Figure 73 4 Verify that the alignment washers are properly aligned and seated in the vertical mounting...

Страница 57: ...bles Zoning configuration setting is also shown for each configuration For E platforms and pre configured systems also refer to Section C 2 Enclosure Labels for information on determining enclosure po...

Страница 58: ...4 Figure 99 5 Figure 100 10 Figure 101 20 Figure 102 SFA12KXE SFA12K 20E SS7000 1 Figure 103 2 Figure 104 3 Figure 105 4 Figure 106 5 Figure 107 10 Figure 108 20 Figure 109 SS8460 1 Figure 110 2 Figur...

Страница 59: ...onfiguration Guide 59 Figure 75 SFA12K 20 Configuration with 1 x SS7000 Enclosure 012 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 112 102 Controller 1 Zone 0 Zone 1 Zo...

Страница 60: ...ure 76 SFA12K 20 Configuration with 2 x SS7000 Enclosures 020 010 012 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 110 112 102 Controller 1 020 010 120 110 I O Modu...

Страница 61: ...x SS7000 Enclosures 020 022 010 012 000 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 122 110 112 100 102 Controller 1 020 010 120 110 I O Module A I O Module B Disk...

Страница 62: ...2 000 001 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 121 122 110 112 100 101 102 Controller 1 020 010 120 110 I O Module A I O Module B Disk Enclosure 02 022 000...

Страница 63: ...I O Module A I O Module B Disk Enclosure 01 Controller 0 120 121 122 110 112 113 100 101 102 103 Controller 1 020 010 120 110 I O Module A I O Module B Disk Enclosure 02 022 000 122 100 I O Module A I...

Страница 64: ...03 020 120 I O Module A I O Module B Disk Enclosure 04 000 100 I O Module A I O Module B Disk Enclosure 05 022 122 I O Module A I O Module B Disk Enclosure 06 001 101 I O Module A I O Module B Disk En...

Страница 65: ...10 065 022 165 122 I O Module A I O Module B Disk Enclosure 11 065 165 I O Module A I O Module B Disk Enclosure 12 066 001 166 101 I O Module A I O Module B Disk Enclosure 13 066 166 I O Module A I O...

Страница 66: ...nstallation Configuration Guide 66 Figure 82 SFA12K 20 Configuration with 1 SS8460 Enclosure 012 002 Controller 0 112 102 Controller 1 012 002 I O Module A Disk Enclosure 01 112 102 I O Module B No of...

Страница 67: ...ure 83 SFA12K 20 Configuration with 2 SS8460 Enclosures 020 010 012 002 Controller 0 120 110 112 102 Controller 1 020 010 I O Module A Disk Enclosure 02 120 110 I O Module B 012 002 I O Module A Disk...

Страница 68: ...SS8460 Enclosure 020 022 010 012 000 002 Controller 0 120 122 110 112 100 102 Controller 1 022 000 I O Module A Disk Enclosure 03 122 100 I O Module B 020 010 I O Module A Disk Enclosure 02 120 110 I...

Страница 69: ...00 001 002 Controller 0 120 121 122 110 112 100 101 102 Controller 1 021 001 I O Module A Disk Enclosure 04 121 101 I O Module B 022 000 I O Module A Disk Enclosure 03 122 100 I O Module B 020 010 I O...

Страница 70: ...21 122 110 112 113 100 101 102 103 Controller 1 013 003 I O Module A Disk Enclosure 05 113 103 I O Module B 021 001 I O Module A Disk Enclosure 04 121 101 I O Module B 022 000 I O Module A Disk Enclos...

Страница 71: ...Enclosure 10 113 I O Module B 003 I O Module A Disk Enclosure 09 103 I O Module B 021 I O Module A Disk Enclosure 08 121 I O Module B 001 I O Module A Disk Enclosure 07 101 I O Module B 020 021 022 01...

Страница 72: ...168 103 I O Module B 068 I O Module A Disk Enclosure 18 168 I O Module B 069 013 I O Module A Disk Enclosure 19 169 113 I O Module B 069 I O Module A Disk Enclosure 20 169 I O Module B 020 021 022 010...

Страница 73: ...uration Guide 73 Figure 89 SFA12KX 12K 40 Configuration with 1 x SS7000 Enclosure 012 002 042 032 012 002 142 132 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 032 042 112 102 Contr...

Страница 74: ...with 2 x SS7000 Enclosures 020 010 012 002 042 032 012 002 142 132 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 050 040 020 010 150 140 120 110 I O Module A I O Module B Disk Encl...

Страница 75: ...2 032 012 002 142 132 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 050 040 020 010 150 140 120 110 I O Module A I O Module B Disk Enclosure 02 052 030 022 000 152 130 122 100 I O M...

Страница 76: ...Module B Disk Enclosure 01 Controller 0 050 040 020 010 150 140 120 110 I O Module A I O Module B Disk Enclosure 02 052 030 022 000 152 130 122 100 I O Module A I O Module B Disk Enclosure 03 051 031...

Страница 77: ...40 020 010 150 140 120 110 I O Module A I O Module B Disk Enclosure 02 052 030 022 000 152 130 122 100 I O Module A I O Module B Disk Enclosure 03 051 031 021 001 151 131 121 101 I O Module A I O Modu...

Страница 78: ...ure 05 052 022 152 122 I O Module A I O Module B Disk Enclosure 06 031 001 131 101 I O Module A I O Module B Disk Enclosure 07 051 021 151 121 I O Module A I O Module B Disk Enclosure 08 033 003 133 1...

Страница 79: ...O Module A I O Module B Disk Enclosure 11 075 065 175 165 I O Module A I O Module B Disk Enclosure 12 076 031 066 001 176 131 166 101 I O Module A I O Module B Disk Enclosure 13 076 066 176 166 I O Mo...

Страница 80: ...guration Guide 80 Figure 96 SFA12KX 12K 40 Configuration with 1 SS8460 Enclosure 042 032 012 002 I O Module A Disk Enclosure 01 142 132 112 102 I O Module B 112 102 Controller 1 012 002 Controller 0 0...

Страница 81: ...n with 2 SS8460 Enclosures 050 040 020 010 I O Module A Disk Enclosure 02 150 140 120 110 I O Module B 042 032 012 002 I O Module A Disk Enclosure 01 142 132 112 102 I O Module B 120 110 112 102 Contr...

Страница 82: ...A Disk Enclosure 03 152 130 122 100 I O Module B 050 040 020 010 I O Module A Disk Enclosure 02 150 140 120 110 I O Module B 042 032 012 002 I O Module A Disk Enclosure 01 142 132 112 102 I O Module B...

Страница 83: ...30 022 000 I O Module A Disk Enclosure 03 152 130 122 100 I O Module B 050 040 020 010 I O Module A Disk Enclosure 02 150 140 120 110 I O Module B 042 032 012 002 I O Module A Disk Enclosure 01 142 13...

Страница 84: ...21 101 I O Module B 052 030 022 000 I O Module A Disk Enclosure 03 152 130 122 100 I O Module B 050 040 020 010 I O Module A Disk Enclosure 02 150 140 120 110 I O Module B 042 032 012 002 I O Module A...

Страница 85: ...Module B 033 003 I O Module A Disk Enclosure 09 133 103 I O Module B 051 021 I O Module A Disk Enclosure 08 151 121 I O Module B 031 001 I O Module A Disk Enclosure 07 131 101 I O Module B 020 021 022...

Страница 86: ...A Disk Enclosure 20 179 169 I O Module B 020 021 022 010 012 013 000 001 002 003 Controller 0 070 032 060 002 I O Module A Disk Enclosure 01 170 132 160 102 I O Module B 070 060 I O Module A Disk Enc...

Страница 87: ...allation Configuration Guide 87 Figure 103 SFA12KXE 12K 20E Configuration with 1 x SS7000 Enclosure 012 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 112 102 Controller...

Страница 88: ...104 SFA12KXE 12K 20E Configuration with 2 x SS7000 Enclosures 020 010 012 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 110 112 102 Controller 1 020 010 120 110 I O...

Страница 89: ...h 3 x SS7000 Enclosures 020 022 010 012 000 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 122 110 112 100 102 Controller 1 020 010 120 110 I O Module A I O Module B...

Страница 90: ...0 012 000 001 002 012 002 112 102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 121 122 110 112 100 101 102 Controller 1 020 010 120 110 I O Module A I O Module B Disk Enclosure 02 022...

Страница 91: ...102 I O Module A I O Module B Disk Enclosure 01 Controller 0 120 121 122 110 112 113 100 101 102 103 Controller 1 020 010 120 110 I O Module A I O Module B Disk Enclosure 02 022 000 122 100 I O Module...

Страница 92: ...10 110 I O Module A I O Module B Disk Enclosure 03 020 120 I O Module A I O Module B Disk Enclosure 04 000 100 I O Module A I O Module B Disk Enclosure 05 022 122 I O Module A I O Module B Disk Enclos...

Страница 93: ...sure 10 065 022 165 122 I O Module A I O Module B Disk Enclosure 11 065 165 I O Module A I O Module B Disk Enclosure 12 066 001 166 101 I O Module A I O Module B Disk Enclosure 13 066 166 I O Module A...

Страница 94: ...lation Configuration Guide 94 Figure 110 SFA12KXE 12K 20E Configuration with 1 x SS8460 Enclosure 012 002 Controller 0 112 102 Controller 1 012 002 I O Module A Disk Enclosure 01 112 102 I O Module B...

Страница 95: ...111 SFA12KXE 12K 20E Configuration with 2 SS8460 Enclosures 020 010 012 002 Controller 0 120 110 112 102 Controller 1 020 010 I O Module A Disk Enclosure 02 120 110 I O Module B 012 002 I O Module A...

Страница 96: ...h 3 SS8460 Enclosures 020 022 010 012 000 002 Controller 0 120 122 110 112 100 102 Controller 1 022 000 I O Module A Disk Enclosure 03 122 100 I O Module B 020 010 I O Module A Disk Enclosure 02 120 1...

Страница 97: ...012 000 001 002 Controller 0 120 121 122 110 112 100 101 102 Controller 1 021 001 I O Module A Disk Enclosure 04 121 101 I O Module B 022 000 I O Module A Disk Enclosure 03 122 100 I O Module B 020 01...

Страница 98: ...110 112 113 100 101 102 103 Controller 1 013 003 I O Module A Disk Enclosure 05 113 103 I O Module B 021 001 I O Module A Disk Enclosure 04 121 101 I O Module B 022 000 I O Module A Disk Enclosure 03...

Страница 99: ...isk Enclosure 10 113 I O Module B 003 I O Module A Disk Enclosure 09 103 I O Module B 021 I O Module A Disk Enclosure 08 121 I O Module B 001 I O Module A Disk Enclosure 07 101 I O Module B 020 021 02...

Страница 100: ...17 168 103 I O Module B 068 I O Module A Disk Enclosure 18 168 I O Module B 069 013 I O Module A Disk Enclosure 19 169 113 I O Module B 069 I O Module A Disk Enclosure 20 169 I O Module B Controller...

Страница 101: ...he module should be installed in For example ENCL 01 means the disk should be installed in the enclosure labeled ENCLOSURE 01 Refer to Section C 2 for more information on enclosure positions in rack T...

Страница 102: ...hows the enclosure positions for systems using up to 10 disk enclosures Figure 122 shows the enclosure positions for systems using 20 disk enclosures Figure 119 84 Bay Enclosure Disk Slot Numbering 01...

Страница 103: ...NCLOSURE 06 ENCLOSURE 07 ENCLOSURE 08 ENCLOSURE 09 ENCLOSURE 10 Controller 0 Controller 1 Figure 122 Enclosure Positions in Rack Front View ENCLOSURE 01 ENCLOSURE 02 ENCLOSURE 03 ENCLOSURE 04 ENCLOSUR...

Страница 104: ...om the Controllers menu select Show Controllers Select to display the primary controller details Note down the controller ID 2 From the Enclosures menu select Show Enclosures Select to display the pri...

Страница 105: ...tivation key is displayed if the license is activated successfully Note down this key You may save and or print a copy of the activation key 7 From the Subsystem menu select Set Subsystem Attributes E...

Страница 106: ...Corporate Headquarters 9351 Deering Avenue Chatsworth CA 91311 ddn com Phone 1 818 700 7600 Fax 1 818 700 7601...

Отзывы: