Datacolor CONDITIONER™ (MB2) 06/2017
page 46/126
7.
Set-point entry in “Fixed value” operating mode
In Fixed value operating mode you can enter a temperature set-point, a humidity set-point, the fan speed,
and the switching-state of up to 16 operation lines.
All settings made in Fixed value operating mode remain valid until the next manual change. They are
saved also when turning off the cabinet or in case of toggling to Idle Mode or Program Mode.
Cabinet without
lights
Setting ranges
Control ranges
Temperature
-5 °C /
41 °F
up to 70 °C /
158 °F.
0 ºC /
32 °F
up to 70 °C /
158 °F
without humidity
10 °C /
50 °F
up to 70 °C /
158 °F
with humidity
Humidity
0 % r.H. up to 80 % r.H.
10 % r.H. to 80 % r.H.
see climatic diagrams, chap. 17.
Fan speed
40% up to 100 %
Cabinet with
lights
Setting ranges
Control ranges
Temperature
-5 °C /
41 °F
up to 50 °C /
122 °F.
0 ºC /
32 °F
up to 50 °C /
122 °F
without humidity
10 °C /
50 °F
up to 50 °C /
122 °F
with humidity
Humidity
0 % r.H. up to 70 % r.H.
10 % r.H. to 70 % r.H.
see climatic diagrams, chap. 17.
Light intensity
0 % to 100 %
Fan speed
40% up to 100 %
Reduce the fan speed only if required, because the spatial distribution of temperature and
humidity will also be reduced.
Technical data refers to 100% fan speed.
For the control range of temperature and relative humidity, see the temperature / humidity diagrams chap.
17).
With set-point type “
Limit
”, adapt the safety controller (chap. 12.2) always when you changed
the temperature set-point. Set the safety controller set-point by approx. 2 °C to 5 °C above the
controller temperature set-point.
Recommended setting: Set-point type “
Offset
” with safety controller set-point 2 °C.
When operating without humidity by setting “Control off” (chap. 6.3), the humidity tolerance
range function is automatically deactivated.
When operating without humidity by activated operation line “Humidity off” (chap. 7.3), set the
humidity tolerance range to “0” in order to avoid tolerance range alarms (chap. 11.4).
Содержание 9020-0129
Страница 124: ...Datacolor CONDITIONER MB2 06 2017 page 124 126 23 7 Dimensions size 115 ...
Страница 125: ...Datacolor CONDITIONER MB2 06 2017 page 125 126 24 EU Declaration of Conformity ...
Страница 126: ...Datacolor CONDITIONER MB2 06 2017 page 126 126 ...