8
P2-17 TXD_232
RS-232 transmit data to external device
<24V / Not Rated
P2-18 RXD_232
RS-232 receive data from external device
<24V / Not Rated
P2-19 GND
RS-232 ground
<24V / Not Rated
P2-20 SHIELD
Internally connected to EARTH; cable shield for analog
monitor signals
Ground
P2-21 4-20mA signal from transducer; - signal at pin P2-23;
internal 250
Ω
shunt permanently connected
<24V / Not Rated
P2-22 0-5VDC or 0-10VDC or 4-20mA signal from
transducer; - signal at pin P2-23; jump pin P2-24 to P2-
23 to use as a 4-20mA input
<24V / Not Rated
P2-23 ANALOG-
- signal return for both at P2-22 and
at P2-21
<24V / Not Rated
P2-24 SHUNT
250
Ω
shunt resistor; jump to P2-23 to use a 4-20mA
signal for at P2-22
<24V / Not Rated
Bottom Rear Connector: P4 (Pump Controller Mode)
PIN#
Name
Description
Electrical Rating
P4-1
Unused
Reserved for future use; do not connect
Not Connected
P4-2
RS485_GND
RS-485 serial ground reference
<24V / Not Rated
P4-3
RS485_B
RS-485 serial interface B
<24V / Not Rated
P4-4
RS485_A
RS-485 serial interface A
<24V / Not Rated
P4-5
SHIELD
Internally connected to EARTH; Cable shield for
RS-485 or RS-232
Ground
P4-6
EX_GND_RAD
RS-232 signal ground
<24V / Not Rated
P4-7
RTS_RAD
RS-232 Request to send
<24V / Not Rated
P4-8
EX_TXD_RAD
RS-232 transmit data to external device
<24V / Not Rated
P4-9
EX_RXD_RAD
RS-232 receive data from external device
<24V / Not Rated
P4-10 CTS_RAD
RS-232 clear to send
<24V / Not Rated
P4-11 SDI12_GND
SDI-12 return/ground
<24V / Not Rated
P4-12 SDI12_DATA
SDI-12 data
<24V / Not Rated
P4-13 SDI12_PWR
12VDC power supply for SDI-12 bus devices
<24V / Not Rated
P4-14 Unused
Reserved for future use; do not connect
Not Connected
Safety Precautions
Review the following statements before installing, servicing, or replacing the Telemetry Control Unit or
any of its components.
General Precautions
•
Only trained and qualified personnel should install, service, or replace this equipment.
•
Carefully read the installation and wiring instructions before connecting the TCU to its power
source.
•
Do not work on the TCU, or connect or disconnect any of its cables, during periods of lightning
activity.
•
To prevent overheating the TCU, do not operate it in an area that exceeds the maximum
recommended temperature of -10°C to 60°C (14°F to 140°F). The upper temperature limit is
50°C (122°F) when using the recommended backup battery.