6
P1-8
BAT+
Backup battery positive terminal
<24V / Not Rated
P1-9
BAT-
Backup battery negative terminal
<24V / Not Rated
P1-10 BEMGND
Isolated ground (wire to BEM001, pin 12)
<24V / Not Rated
P1-11 BEM_PWR
Isolated power (wire to BEM001, pin 10)
<24V / Not Rated
P1-12 BEM_CTS
Isolated clear to send (wire to BEM001, pin 6) <24V / Not Rated
P1-13 BEM_RXD
Isolated receive data (wire to BEM001, pin 4)
<24V / Not Rated
P1-14 BEM_TXD
Isolated transmit data (wire to BEM001, pin 2) <24V / Not Rated
P1-15 BEM_RTS
Isolated request to send (wire to BEM001, pin
8)
<24V / Not Rated
P1-16 ALM_HORN Load side of alarm horn relay (NO)
120VAC, 60HZ, 1A,
0-24VDC, 1A
P1-17 ALM_LITE
Load side of alarm light relay (NC)
120VAC, 60HZ, 1A,
0-24VDC, 1A
P1-18 ALM_PWR
Line side of alarm relays
120VAC, 60HZ, 2A,
0-24VDC, 2A
P1-19 AUX_OUT
Load side of auxiliary relay
120-240VAC, 60HZ, 1A,
Pilot Duty
P1-20 AUX_PWR
Line side of auxiliary relay
120-240VAC, 60HZ, 1A
P1-21 MTR3_STR
Load side of motor starter 3 relay
120-240VAC, 60HZ, 1A,
Pilot Duty
P1-22 MTR2_STR
Load side of motor starter 2 relay
120-240VAC, 60HZ, 1A,
Pilot Duty
P1-23 MTR1_STR
Load side of motor starter 1 relay
120-240VAC, 60HZ, 1A,
Pilot Duty
P1-24 STRT_PWR
Line side of motor starter relays
120-240VAC, 60HZ, 3A
Top Rear Connector: P3 (Pump Controller Mode)
PIN#
Name
Description
Electrical Rating
P3-1
C_CT+
C-phase current transformer positive connection
<24V / Not Rated
P3-2
C_CT-
C-phase current transformer negative connection
<24V / Not Rated
P3-3
B_CT+
B-phase current transformer positive connection
<24V / Not Rated
P3-4
B_CT-
B-phase current transformer negative connection
<24V / Not Rated
P3-5
A_CT+
A-phase current transformer positive connection
(wye setup only)
<24V / Not Rated
P3-6
A_CT-
A-phase current transformer negative connection
(wye setup only)
<24V / Not Rated
P3-7
0-5VDC or 0-10VDC or 4-20mA signal from
transducer; return signal at P3-8; jump
P3-9 to P3-8 to use as a
4-20mA input
<24V / Not Rated
P3-8
ANALOG3-
- return signal for (P3-7)
<24V / Not Rated
P3-9
SHUNT
250
Ω
shunt resistor; jump to P3-8 to use a
4-20mA signal for (P3-7)
<24V / Not Rated
P3-10
0-5VDC or 0-10VDC or 4-20mA signal from
transducer; return signal at P3-11; jump P3-12 to P3-
11 to use as a 4-20mA input
<24V / Not Rated
P3-11 ANALOG4-
- return signal for (P3-10)
<24V / Not Rated
P3-12 SHUNT
250
Ω
shunt resistor; jump to P3-11 to use a 4-20mA
signal for (P3-10)
<24V / Not Rated
Содержание TCU800
Страница 1: ...T C U 8 0 0 Q u i c k S t a r t G u i d e Data Flow Systems Inc...
Страница 23: ...22 Notes...
Страница 24: ...23 Notes...
Страница 25: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne FL 32934 321 259 5009 www dataflowsys com...