background image

 

 

 

Pa

ge

GENERAL 

INFORMATION 

GENERAL REMARKS 

 

 

 

This  manual  is  an  integral  part  of  the  machine,  therefore  it  should  always  be  carefully  kept  and  it  should  always  be 
provided together with the machine, if it is transferred to another owner or user. If this manual is damaged or lost, a new 
one should be requested from the local Technical Assistance Service or from the Manufacturer. 
 
After  unpacking  the  product,  check  the integrity and  completeness of the  contents.  If  not, contact  the  Agency that  sold 
the unit. 
 
The installation of the appliance must be carried out by an authorized company which, at the end of the work, issues to 
the owner the Declaration of Conformity of Installation made in accordance with the rules, therefore in accordance with 
the Standards and the instructions provided by the Manufacturer in this instruction manual. 
 
This  appliance  has  been  manufactured  for  room  heating  and  it  must  be  used  for  this  purpose,  compatibly  with  its 
performance characteristics. 
 
Any contractual or extra-contract liability of the Producer in respect of damages caused to people, animal or things by a 
non correct installation, setting or maintenance or by the improper use of the machine is excluded. 
 
If  the  temperature  is  too  high,  it could be harmful  to health and  would  be  a useless  waste  of  energy.  Do not leave the 
rooms closed for a long time. Periodically open the windows to ensure proper ventilation. 
 
During the initial start-up, there may be the formation of odours and fumes due to the evaporation of the liquid added to 
protect the heat exchanger during storage; this is normal and it will disappear after a short period. It is recommended to 
suitably ventilate the room. 
 
If you will not be using the unit for long periods, carry out the following operations: 

  turn the main switch of the unit and the general switch of the plant to "OFF" 

  close the main fuel supply valve 

 
In  case  of  long  periods  during  which  the  equipment  is  not  operated,  it  is  recommended  to  contact  either  After-Sales 
Technical Assistance Service or anyhow professionally qualified personnel for its new start-up. 
 
The machine shall be fitted only with original accessory equipment. The Producer is not liable for damages arising from 
the improper use of the machine or from the use of non-original materials or accessories. 
 
References  to  Laws,  Regulations,  Directives  and  Technical  Rules  mentioned  in  this  manual  are  provided  only  for 
information  purposes  and  as  they  are  in  force  when  the  manual  is  printed.  The  entry  into  force  of  new  provisions  or 
amendments to current laws does not represent an obligation of the manufacturer towards third parties. 
 
Repairs or maintenance must be performed by the Technical Assistance Service or by qualified personnel in accordance 
with  this  manual.  Do  not  modify  or  tamper  with  the  appliance  as  dangerous  situations  can  be  created  and  the 
manufacturer will not be liable for any damage caused. 
 
The systems that are to be created (gas pipes, power supply, etc.) must be suitably secured and must not be dangerous 
with the risk of tripping. 
 
The  Producer is  responsible for  the  product  compliance  with  Laws,  Directives  or  Construction  Rules  in  force  when  the 
product  is  marketed.  The  knowledge  and  observance  of  the  laws  and  standards  regarding  plant  design,  installation, 
operation and maintenance are the sole responsibility of the designer, installer and user. 
 
The  Producer  shall  not  be  held  responsible  for  failure  to  comply  with  the  instructions  of  this  manual,  for  the 
consequences of any operations carried out and not specifically provided for or for translations open to misinterpretation. 
 
The electrical system must feature suitable individual and independent electrical protections for each appliance which, in 
case of accidental failure, will be activated on the single appliance without prejudice to the proper operation of the other 
units present on the installation. 
 

The  appliance  is  designed  to  be  operated  with  the  heating  capacity  and  the  air  flow  rate  specified  in  the  Data 
Sheet chapter. If the heating capacity is too low and/or the air flow rate is too high, combustion products may 
condensate,  resulting  in  the  irreparable  corrosion  of  the  heat  exchanger.  If  the  heating  capacity  is  too  high 
and/or the air flow rate is too low, an anomalous overheating of the heat exchanger may occur, resulting in the 
activation of the safety devices and causing damage to the exchanger 

 

Содержание Master BF 105

Страница 1: ...P 1 INSTALLATION AND OPERATION SERIES BF INSTALLATION AND OPERATION...

Страница 2: ...RAL INFORMATION COMPLIANCE The hot air generator mod BF complies with Machinery directive 2006 42 EC Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Regulation 201...

Страница 3: ...g 17 Fuel connection 17 Fume exhaust 18 Combustion air 19 Assembly of diesel burner 19 Burner control 20 Wiring 20 Electrical power supply 21 Wiring diagram reference 21 Control panel 22 Fuel tank 22...

Страница 4: ...shall be fitted only with original accessory equipment The Producer is not liable for damages arising from the improper use of the machine or from the use of non original materials or accessories Ref...

Страница 5: ...within the reach of children the packaging materials cardboard staples plastic bags etc as they may be potentially dangerous Do not install the unit near flammable material or in rooms with an aggres...

Страница 6: ...decreasing section and with opposing turbulencing prints Steel flue gas manifold equipped with an inspection door External casing The casing consists of panels in pre painted and or powder coated shee...

Страница 7: ...eration GENERAL INFORMATION IDENTIFICATION The warm air heaters can be identified through The Technical Plate applied on the machine specifying the main technical performance data In the event of dama...

Страница 8: ...nt 3 Diesel filter where present 4 Filler neck where present 5 Diesel burner 6 Electrical panel 7 Fan 8 Fan support 9 Diaphragm 10 Deflector 11 Deflector 12 Deflector 13 Panel 14 Side panel 15 Beam 16...

Страница 9: ...rform an inversion in the combustion chamber are routed to the first exhaust manifold front manifold and are channelled in the exchange elements smoke pipes arrive in the second exhaust manifold rear...

Страница 10: ...e 10 GENERAL INFORMATION DIMENSIONS AND WEIGHT TYPE A B C D NET WEIGHT1 mm mm mm mm mm kg 1 1 020 500 1 600 1 240 120 140 2 1 120 540 1 700 1 320 150 180 3 1 400 760 2 000 1 580 180 315 1 Without burn...

Страница 11: ...800 5 300 8 800 Nominal air thermal gradient K 29 32 31 FAN thermostat calibration C 35 35 35 LIMIT thermostat calibration C 100 100 100 Sound pressure emission 4 dB A 57 60 70 Range of use C 5 40 5...

Страница 12: ...ow 90 6 89 7 89 9 s h 72 3 72 1 72 9 Legend P rated h Nominal heating capacity P rated h Minimum heating capacity nom Nominal heating capacity useful efficiency pl Minimum capacity useful efficiency e...

Страница 13: ...to the width of the machine If belts or ropes are used a rocker arm must be used not included to prevent the pressure exerted by the same from damaging the structure of the unit Should it be necessar...

Страница 14: ...g and maintenance operations maintain the safety distances from flammable material be placed close to a flue chimney be able to be connected to the fuel source be close to an electrical socket allow f...

Страница 15: ...ter wall with delivery on 3 sides In the corner with delivery on 2 sides Any restrictions deriving from specific Laws and regulations must also be observed for example regarding fires Refer to the des...

Страница 16: ...e upper surface of the plenum can not be stepped on Air can not be spread from only one side of the plenum GENERAL INFORMATION ACCESSORIES Any accessories must be original To install them follow the i...

Страница 17: ...ut hole TYPE 1 2 3 pre cut hole mm 150 150 300 1 Pre cut hole 2 Circular fitting with stop not supplied 3 Secondary channelling not supplied INSTALLATION INFORMATION FUEL CONNECTION The machine should...

Страница 18: ...he entire smoke duct must not rest on the appliance The flue must ensure the minimum depression required by the current technical standards considering zero pressure to the connection with the fume du...

Страница 19: ...be installed in accordance with the regulations in force and be used only in a sufficiently ventilated area Check that the combustion air inlet is always free from any obstacles leaves sheets of pape...

Страница 20: ...y sized according to the regulations in force Always connect the earthing system taking care to leave the earth wire slightly longer that the other wires so that in case of accidental pulling the latt...

Страница 21: ...is an integral part of this instruction manual We recommend keeping it carefully together with the other documents Should this copy be mislaid ask the Manufacturer for a duplicate notifying the serial...

Страница 22: ...thermostat reset button 6 Room thermostat adjustment knob INSTALLATION INFORMATION FUEL TANK Type 1 and 2 appliances feature a built in tank The type 3 appliance for reasons of operating autonomy mus...

Страница 23: ...tected and solved In case of doubt please contact the closest Authorized Assistance Centre which will provide you with the necessary technical assistance INSTALLATION INFORMATION VENTILATION HEATING O...

Страница 24: ...valve and make sure the burner stops During the first start up cycle the burner may stop due to the lack of fuel supply In this case wait at least 30 seconds and after unblocking the burner by pressi...

Страница 25: ...the burner turns off Do not intervene on the sealings made in the factory check that the engine electric absorption value does not exceed the value specified in the plate make sure that the fan operat...

Страница 26: ...rder for the machine to properly work and be maintained we suggest performing the regular cleaning and maintenance operations according to the indications in the following paragraphs Cleaning and main...

Страница 27: ...Check the functionality of the safety thermostat at least quarterly Simulate its intervention and it should be verified that the burner goes out MAINTENANCE INFORMATION SECURITY CONTROL Periodically...

Страница 28: ...d the door 10 after loosening the nuts 9 Using a brush clean the inside of the smoke pipes Using an aspirator remove any soot that has deposited in the rear flue gas collector and in the combustion ch...

Страница 29: ...ce Toode Produsul V ro bok Proizvod BF 35 BF 75 BF 105 Wedeclarethatitiscompliantwith Sidichiarache conformea EswirdalskonformmitdenfolgendenNormen erkl rt Sedeclaraqueest enconformidadcon Nousd claro...

Страница 30: ...Poland Dantherm Sp z o o 5A 62 023 Dantherm LLC ul Transportnaya 22 ownership 2 142802 STUPINO Moscow region Russia 22 2 142802 Dantherm China LTD Unit 2B 512 Yunchuan Rd Shanghai 201906 China Danther...

Отзывы: