background image

 

 

INSTALLATION 

INFORMATION 

BURNER REGULATION 

 

Combination table for pre-calibrated RIELLO burners: 

TYPE 

 

RIELLO burner 

Mod. 

REG 3  R40G10  R40G10 

Nozzle Delavan 60°W 

GPH 

0.60 

1.25 

2.00 

Pump pressure 

bar 

13.0 

11.0 

13.0 

Burner Head Position 

Notch no. 

1.0 

2.0 

5.0 

Air damper position 

Notch no. 

5.0 

4.0 

5.0 

Measured CO

2

 

 12.5 

 12.5 

 12.5 

Measured CO 

ppm 

 5 

 5 

 5 

Net smoke temperature 

°K 

 160 

 160 

 150 

 

 

The  above  data  and  any  pre-calibration  at  the  factory  are  non-binding.  It  is  always 
mandatory to check and adjust the burner at start-up and in the actual conditions of use. 

 

INSTALLATION 

INFORMATION 

ELECTRICAL CONNECTIONS 

 
The machine is provided as standard with the electric panel installed and with the engine, control 
and safety thermostats of the FAN-LIMIT device connected. Therefore, the fitter just has to perform 
the following operations: 

  connection to the general power supply; 

  connections to the blown burner; 

  connections  to  the  various  external  safety  systems  (fire  dampers,  humidifier,  fire  protection, 

etc.). 

 

  Electrical connections must only be carried out by qualified and competent personnel. In case of 

doubt, do not intervene on the appliance and consult the manufacturer. 

  Install  upstream  of  the  unit  a  differential  magneto  thermal  circuit  breaker  suitably  sized 

according to the regulations in force. 

  Always connect the earthing system, taking care to leave the earth wire slightly longer that the 

other wires, so that, in case of accidental pulling, the latter is the last one to be removed. 

  Get  qualified  personnel  to  check  that  the  section  of  the  cables  and  the  electrical  system  are 

suitable for the maximum power absorbed by the unit indicated on the information plate. 

  Respect polarity in the connection of the power supply (phase - neutral). In any case, make sure 

that the direction of rotation of the fans is correct. 

  The unit must be connected to an efficient earthing system. The manufacturer shall not be held 

responsible for any damage caused by failure to earth the appliance. 

  The  electrical  cables  must  be  positioned  so  as  not  to  come  into  contact  with  hot  and/or  cold 

surfaces, or with sharp edges. 

  In  accordance  with  the Standards  regarding the  installation  of  electrical components,  a  device 

that  ensures  disconnection  from  the  mains  with  an  opening  distance  between  contacts  that 
guarantees  complete  disconnection  in  overvoltage  conditions  III  (Standard  EN  60335-1)  must 
be included. 

  It is forbidden to use water pipes or gas pipes to earth the unit. 

  For the input and output of the electrical wires, use the dedicated cable clamps on the unit 

 

The  appliance  must  always  be  electrically  powered.  Operation  consent  must  only  be 
obtained by closing and opening the contact of the room thermostat. 

Pa

ge.

20

 

Содержание Master BF 105

Страница 1: ...P 1 INSTALLATION AND OPERATION SERIES BF INSTALLATION AND OPERATION...

Страница 2: ...RAL INFORMATION COMPLIANCE The hot air generator mod BF complies with Machinery directive 2006 42 EC Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Regulation 201...

Страница 3: ...g 17 Fuel connection 17 Fume exhaust 18 Combustion air 19 Assembly of diesel burner 19 Burner control 20 Wiring 20 Electrical power supply 21 Wiring diagram reference 21 Control panel 22 Fuel tank 22...

Страница 4: ...shall be fitted only with original accessory equipment The Producer is not liable for damages arising from the improper use of the machine or from the use of non original materials or accessories Ref...

Страница 5: ...within the reach of children the packaging materials cardboard staples plastic bags etc as they may be potentially dangerous Do not install the unit near flammable material or in rooms with an aggres...

Страница 6: ...decreasing section and with opposing turbulencing prints Steel flue gas manifold equipped with an inspection door External casing The casing consists of panels in pre painted and or powder coated shee...

Страница 7: ...eration GENERAL INFORMATION IDENTIFICATION The warm air heaters can be identified through The Technical Plate applied on the machine specifying the main technical performance data In the event of dama...

Страница 8: ...nt 3 Diesel filter where present 4 Filler neck where present 5 Diesel burner 6 Electrical panel 7 Fan 8 Fan support 9 Diaphragm 10 Deflector 11 Deflector 12 Deflector 13 Panel 14 Side panel 15 Beam 16...

Страница 9: ...rform an inversion in the combustion chamber are routed to the first exhaust manifold front manifold and are channelled in the exchange elements smoke pipes arrive in the second exhaust manifold rear...

Страница 10: ...e 10 GENERAL INFORMATION DIMENSIONS AND WEIGHT TYPE A B C D NET WEIGHT1 mm mm mm mm mm kg 1 1 020 500 1 600 1 240 120 140 2 1 120 540 1 700 1 320 150 180 3 1 400 760 2 000 1 580 180 315 1 Without burn...

Страница 11: ...800 5 300 8 800 Nominal air thermal gradient K 29 32 31 FAN thermostat calibration C 35 35 35 LIMIT thermostat calibration C 100 100 100 Sound pressure emission 4 dB A 57 60 70 Range of use C 5 40 5...

Страница 12: ...ow 90 6 89 7 89 9 s h 72 3 72 1 72 9 Legend P rated h Nominal heating capacity P rated h Minimum heating capacity nom Nominal heating capacity useful efficiency pl Minimum capacity useful efficiency e...

Страница 13: ...to the width of the machine If belts or ropes are used a rocker arm must be used not included to prevent the pressure exerted by the same from damaging the structure of the unit Should it be necessar...

Страница 14: ...g and maintenance operations maintain the safety distances from flammable material be placed close to a flue chimney be able to be connected to the fuel source be close to an electrical socket allow f...

Страница 15: ...ter wall with delivery on 3 sides In the corner with delivery on 2 sides Any restrictions deriving from specific Laws and regulations must also be observed for example regarding fires Refer to the des...

Страница 16: ...e upper surface of the plenum can not be stepped on Air can not be spread from only one side of the plenum GENERAL INFORMATION ACCESSORIES Any accessories must be original To install them follow the i...

Страница 17: ...ut hole TYPE 1 2 3 pre cut hole mm 150 150 300 1 Pre cut hole 2 Circular fitting with stop not supplied 3 Secondary channelling not supplied INSTALLATION INFORMATION FUEL CONNECTION The machine should...

Страница 18: ...he entire smoke duct must not rest on the appliance The flue must ensure the minimum depression required by the current technical standards considering zero pressure to the connection with the fume du...

Страница 19: ...be installed in accordance with the regulations in force and be used only in a sufficiently ventilated area Check that the combustion air inlet is always free from any obstacles leaves sheets of pape...

Страница 20: ...y sized according to the regulations in force Always connect the earthing system taking care to leave the earth wire slightly longer that the other wires so that in case of accidental pulling the latt...

Страница 21: ...is an integral part of this instruction manual We recommend keeping it carefully together with the other documents Should this copy be mislaid ask the Manufacturer for a duplicate notifying the serial...

Страница 22: ...thermostat reset button 6 Room thermostat adjustment knob INSTALLATION INFORMATION FUEL TANK Type 1 and 2 appliances feature a built in tank The type 3 appliance for reasons of operating autonomy mus...

Страница 23: ...tected and solved In case of doubt please contact the closest Authorized Assistance Centre which will provide you with the necessary technical assistance INSTALLATION INFORMATION VENTILATION HEATING O...

Страница 24: ...valve and make sure the burner stops During the first start up cycle the burner may stop due to the lack of fuel supply In this case wait at least 30 seconds and after unblocking the burner by pressi...

Страница 25: ...the burner turns off Do not intervene on the sealings made in the factory check that the engine electric absorption value does not exceed the value specified in the plate make sure that the fan operat...

Страница 26: ...rder for the machine to properly work and be maintained we suggest performing the regular cleaning and maintenance operations according to the indications in the following paragraphs Cleaning and main...

Страница 27: ...Check the functionality of the safety thermostat at least quarterly Simulate its intervention and it should be verified that the burner goes out MAINTENANCE INFORMATION SECURITY CONTROL Periodically...

Страница 28: ...d the door 10 after loosening the nuts 9 Using a brush clean the inside of the smoke pipes Using an aspirator remove any soot that has deposited in the rear flue gas collector and in the combustion ch...

Страница 29: ...ce Toode Produsul V ro bok Proizvod BF 35 BF 75 BF 105 Wedeclarethatitiscompliantwith Sidichiarache conformea EswirdalskonformmitdenfolgendenNormen erkl rt Sedeclaraqueest enconformidadcon Nousd claro...

Страница 30: ...Poland Dantherm Sp z o o 5A 62 023 Dantherm LLC ul Transportnaya 22 ownership 2 142802 STUPINO Moscow region Russia 22 2 142802 Dantherm China LTD Unit 2B 512 Yunchuan Rd Shanghai 201906 China Danther...

Отзывы: