INSTALLATION
INFORMATION
SMOKE DISCHARGE
Fume exhaust connection position and example of connection to the flue:
1.
Condensate discharge fitting
, necessary to prevent any condensate that has formed
in the flue to flow inside the heat exchanger.
▪
The exhaust pipe and the flue connector should be made in compliance with the Regulations
and Laws in force. They should be made up of metal and stiff ducts, capable of resisting to
mechanical, thermal and chemical stress caused by the combustion.
▪
It is mandatory that all components of the flue be certified
▪
To avoid reflux of condensation from the flue to the hot air generator, there must be a
condensation discharge at the lowest point of the smoke duct.
▪
The weight of the entire smoke duct must not rest on the appliance.
▪
The flue must ensure the minimum depression required by the current technical standards,
considering "zero" pressure to the connection with the fume duct.
▪
Non insulated exhaust pipes might be a source of dangers.
▪
Unsuitable or wrongly sized flues or flue gas pipes might amplify the burning noise and affect
negatively the combustion parameters.
▪
Joint seals should be made of materials resistant to the thermal and chemical stress caused by
the combustion products.
▪
If walls and/or covers have to be crossed, this operation should be perfectly carried out,
preventing seepage or fire risks.
▪
The use of pipes made of plastic material is forbidden
IF INSTALLATION IS PROVIDED IN THE AREA OF FREE ACCESS TO PERSONS AND / OR
ANIMALS, THE FLUE PIPE UP TO APROX. 2 METERS ABOVE, MUST BE REALIZED IN
DOUBLE WALL VERSION AND/OR EQUIPPED WITH ANTI-SCALD PERFORATED
NETWORK.