INSTALLATION
INFORMATION
CONTROLS
ROOM THERMOSTAT:
Installed on the appliance, its function is to switch the appliance on and off in order to keep the
temperature close to the set value.
Heating/stop/ventilation mode selector switch:
It is placed in the machine electric panel and it is used to select the operating cycle:
▪
Set the machine on the "heating" symbol, it pre-sets the machine so that the fan and burner will
start automatically when heat is requested.
▪
Set the machine on the "heating" symbol, it pre-sets the machine so that the burner will not
operate. When only the fan is on, it is used for summer cooling.
▪
Set the machine on the "heating" symbol, it stops the warm air heater. The burner works for a
certain period in order to exhaust the heat accumulated in the heat exchanger.
LIMIT thermostat reset button:
Placed on the body of the LIMIT thermostat, its function is to restore the operation of the burner
after it has stopped due to overtemperature.
Before restoring any device, the problem that has triggered the safety protection should be
detected and solved. In case of doubt, please contact the closest Authorized Assistance
Centre, which will provide you with the necessary technical assistance.
INSTALLATION
INFORMATION
VENTILATION / HEATING
Operating cycle in ventilation mode:
The operations to be performed to achieve correct operation in ventilation mode are the following:
▪
power the appliance;
▪
place the switch on "ventilation";
At this point, only the ventilation unit will operate and air at the return temperature will be sent into
the environment.
Operating cycle in heating mode:
The operations to be performed to achieve correct operation in heating mode are the following:
▪
power the appliance
▪
set the room thermostat to the desired temperature
▪
place the switch on "heating"
At this point the burner is electrically powered and, after the pre-washing function of the
combustion chamber, the flame is ignited.
About one minute after the flame is ignited, the ventilation unit starts and hot air is sent into the
environment.
Once the temperature set on the room thermostat has been reached, the burner stops and after
about 4 minutes the ventilation unit stops too.
The entire cycle is repeated automatically each time the temperature drops below the value set on
the room thermostat.
Pa
ge.
23