46512-0999 <90-00083>
P
AGE
39
5.
In the Disable Point 64 Device Failures field, type either an N for
no or a Y for yes. For more information about this feature, refer to
the Extended Device Failure section of this chapter.
6.
Press Enter.
TBOS P
ROTOCOL
The Section Number to Respond field represents the locations in
the MAP’s memory where alarm information is stored, as
defined in the following table:
SECTION
NUMBER
MAP MEMORY
LOCATIONS
SECTION
NUMBER
MAP MEMORY
LOCATIONS
1
1-8
9
65-72
2
9-16
10
73-80
3
17-24
11
81-88
4
25-32
12
89-96
5
33-40
13
97-104
6
41-48
14
105-112
7
49-56
15
113-120
8
57-64
16
121-128
The MAP can report 16 displays of TBOS alarms, eight through
the master port and eight through the printer port. These
displays can be stored in any section number listed above.
To configure the TBOS parameters:
1.
In the Section Number to Respond field, type a section number
from the preceding table.
2.
Press Enter.
3.
In the Disable Point 64 Device Failures field, type either an N for
no or a Y for yes. For more information about this feature, refer to
the Extended Device Failure section of this chapter.
4.
Press Enter.
TABS P
ROTOCOL
To configure the TABS parameters:
1.
In the Address field, enter the address of the 46020 module as set
by switch S1 (master port) or S2 (printer port). The address can be
from 0-31. Press Enter.
2.
In the Max Display field, enter a number from 1-128.
MAP SYSTEM DEFINITION
CONTINUED
. . .