[2] Local/Remote
Application
Local/Remote
130BC431.10
+24V 12
DI1
18
DI2
19
DI3
27
DI4
29
DI5
32
DI6
33
DI7
31
COM 20
+10V 50
AI1
53
-
+
AI2
54
COM 55
AO1 45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Setup select
4-20
mA
Description
For applications
where the speed
reference can be
switched between
local potentiometer
and remote current
signal
Parameter settings Setup 1
Setup 2
0-10 (Active Set-
up)
[9] Multi Set-up
[9] Multi Set-up
0-12 (Link Set-up)
[20] Linked
[20] Linked
1-00 (Configuration
Mode)
[0] Speed Open Loop [0] Speed Open Loop
3-00 (Ref Range)
[0] Min- Max
[0] Min- Max
3-15 (Ref Source 1) [1] AI 53
[2] AI 54
3-16 (Ref Source 2)
4-12 (Motor Low
Limit)
25.0 Hz
25.0 Hz
4-14 (Motor High
Limit)
50.0 Hz
50.0 Hz
5-10 (DI 18
Selection)
[8] Start
[8] Start
5-12 (DI 27
Selection)
[2] Coast Inverse
[2] Coast Inverse
5-14 (DI 32
Selection)
[23] Set-up select
[23] Set-up select
5-40 (Relay 1
Selection)
Running
Running
5-40 (Relay 2
Selection)
Alarm
Alarm
6-10 (AI 53 Low)
0.07 V
6-11 (AI 53 High)
10 V
6-19 (AI 53 Mode)
[1] Voltage Mode
6-22 (AI 54 Low)
4.0 mA
6-23 (AI 54 High)
20.0 mA
6-29 (AI 54 Mode)
[0] Current Mode
6-70 (Term 45
Mode)
[0] 0-20 mA
[0] 0-20 mA
6-71 (AO45)
[100] Output freq
[100] Output freq
6-90 (Term 42
Mode)
[0] 0-20 mA
[0] 0-20 mA
6-91 (AO42)
[103] Motor current
[103] Motor current
Table 1.3
[3] Speed Open Loop
Application
Conveyors, extruders
130BC432.10
+24V 12
DI1
18
DI2
19
DI3
27
DI4
29
DI5
32
DI6
33
DI7
31
COM 20
+10V 50
AI1
53
AI2
54
COM 55
AO1 45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Description
For running at a stable
speed by a voltage
reference signal.
Parameter settings
1-00 (Configuration Mode): [0] Speed Open Loop
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [1] AI 53
4-12 (Motor Low Limit): 25.0 Hz
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27 Selection): [2] Coast Inverse
5-40 (Relay 1 Selection): Running
5-40 (Relay 2 Selection): Alarm
6-10 (AI 53 Low): 0.07 V
6-11 (AI 53 High): 10 V
6-19 (AI 53 Mode): [1] Voltage Mode
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
Table 1.4
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A102 - VLT
®
is a registered Danfoss trademark
5
1
1
Содержание VLTAutomationDrive FC 360
Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT AutomationDrive FC 360 ...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark ...
Страница 51: ...Index VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark 47 ...
Страница 52: ...www danfoss com drives MG06A102 130R0413 MG06A102 Rev 2012 11 14 ...