No.
Description
Warning
Alarm
Trip
Lock
Cause of Problem
54
AMA small motor
X
The motor is too small for the AMA to operate.
55
AMA parameter range
X
The parameter values of the motor are outside of
the acceptable range. AMA will not run.
56
AMA interrupt
X
The user has interrupted the AMA.
57
AMA timeout
X
58
AMA internal
X
X
Contact your Danfoss supplier.
59
Current limit
X
X
VLT overload.
61
Encoder loss
X
X
63
Mechanical Brake Low
X
Actual motor current has not exceeded “release
brake” current within “start delay” time window.
65
Control card temp
X
X
X
The cutout temperature of the control card is 80 °C.
66
Heat sink Temperature Low
X
The frequency converter is too cold to operate. This
warning is based on the temperature sensor in the
IGBT module.
70
Illegal FC config
X
X
The control card and power card are incompatible.
79
Undefined
X
X
80
Drive Initialised to Default Value
X
All parameter settings are initialized to default
settings.
87
Auto DC braking
X
Occurs when copying from LCP if the LCP contains
erroneous data - or if no data was uploaded to the
LCP.
95
Broken belt
X
X
101
Flow/pressure info missing
X
X
250
New sparepart
X
X
A component in the frequency converter has been
replaced.
251
New typecode
X
X
The power card or other components have been
replaced and the typecode changed.
nw
run
Not While RUNning
Parameter can only be changed when the motor is
stopped.
Err.
A wrong password was entered
Occurs when using a wrong password for changing
a password-protected parameter.
1)
These faults may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.
Table 6.1 Warnings and Alarms Code List
Warnings and Alarms
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A102 - VLT
®
is a registered Danfoss trademark
33
6
6
Содержание VLTAutomationDrive FC 360
Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT AutomationDrive FC 360 ...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark ...
Страница 51: ...Index VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark 47 ...
Страница 52: ...www danfoss com drives MG06A102 130R0413 MG06A102 Rev 2012 11 14 ...