8.2 General Technical Data
Mains Supply (L1, L2, L3)
Supply Terminals
L1, L2, L3
Supply voltage
380-480 V:-15 (-25)
1)
to +10%
1) The frequency converter can run at -25% input voltage with reduced performance. The maximum output power of the
frequency converter is 75% in case of -25% input voltage and 85% in case of -15% input voltage.
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW
maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
maximum 1 time/min.
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480 V maximum.
Motor Output (U, V, W)
Output voltage
0-100% of supply voltage
Output frequency (0.37-75 kW)
0-500 Hz
Output frequency in VVC
plus
Mode
0-200 Hz
Switching on output
Unlimited
Ramp times
0.01-3600 s
1)
Voltage and power dependent
Torque Characteristics
Starting torque (Constant torque)
maximum 160% for 60 s
1)
Overload torque (Constant torque)
maximum 160% for 60 s
1)
Starting torque (Variable torque)
maximum 110% for 60 s
1)
Overload torque (Variable torque)
maximum 110% for 60 s
Starting current
maximum 200% for 1 s
Torque rise time in VVC
plus
(independent of fsw)
10 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Control Cable Lengths and Cross Sections
1)
Max. motor cable length, screened
50 m
Max. motor cable length, unscreened
100 m
Maximum cross section to control terminals, flexible/ rigid wire
2.5mm
2
/14 AWG
Minimum cross section to control terminals
0.55 mm
2
/ 30AWG
1)
For power cables, see electrical data tables.
Digital Inputs
Programmable digital inputs
7
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33, 31
Logic
PNP or NPN
Voltage level
0 - 24 V DC
Voltage level, logic'0' PNP
< 5 V DC
Voltage level, logic'1' PNP
> 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Maximum voltage on input
28 V DC
Specifications
VLT
®
AutomationDrive FC 360 Quick Guide
38
MG06A102 - VLT
®
is a registered Danfoss trademark
8
8
Содержание VLTAutomationDrive FC 360
Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT AutomationDrive FC 360 ...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark ...
Страница 51: ...Index VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark 47 ...
Страница 52: ...www danfoss com drives MG06A102 130R0413 MG06A102 Rev 2012 11 14 ...