![Danfoss VLTAutomationDrive FC 360 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/danfoss/vltautomationdrive-fc-360/vltautomationdrive-fc-360_quick-manual_507919032.webp)
5 Wiring Examples
The examples in this section are intended as a quick
reference for common functionalities.
Parameters
FC
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
130BD063.10
Function
Setting
1-29 Automatic
Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
5-12 Terminal 27
Digital Input
[2]* Coast
inverse
* = Default Value
Notes/comments: Parameter
group 1-2* must be set
according to motor
NOTE
If terminal 12 and 27 are
not connected, set 5-12 to
[0]
Table 5.1 AMA with T27 Connected
Parameters
130BD064.10
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
-10 - +10V
+
-
FC
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
6-19 Terminal 53
Mode
[1] Voltage
* = Default Value
Notes/comments:
Table 5.2 Analog Speed Reference (Voltage)
Parameters
130BD065.10
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
4 - 20mA
+
-
FC
Function
Setting
6-12 Terminal 53
Low Current
4 mA*
6-13 Terminal 53
High Current
20 mA*
6-14 Terminal 53
Low Ref./Feedb.
Value
0 RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
6-19 Terminal 53
Mode
[0] current
* = Default Value
Notes/comments:
Table 5.3 Analog Speed Reference (Current)
Parameters
130BD066.10
FC
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
Function
Setting
5-10 Terminal 18
Digital Input
[8] Start
5-11 Terminal 19
Digital Input
[10]
Reversing*
5-12 Terminal 27
Digital Input
[0] No
operation
5-14 Terminal 32
Digital Input
[16] Preset
ref bit 0
5-15 Terminal 33
Digital Input
[17] Preset
ref bit 1
3-10 Preset
Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
* = Default Value
Notes/comments:
Table 5.4 Start/Stop with Reversing and 4 Preset Speeds
Wiring Examples
VLT
®
AutomationDrive FC 360 Quick Guide
28
MG06A102 - VLT
®
is a registered Danfoss trademark
5
5
Содержание VLTAutomationDrive FC 360
Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT AutomationDrive FC 360 ...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark ...
Страница 51: ...Index VLT AutomationDrive FC 360 Quick Guide MG06A102 VLT is a registered Danfoss trademark 47 ...
Страница 52: ...www danfoss com drives MG06A102 130R0413 MG06A102 Rev 2012 11 14 ...