Mains Supply 3x525-690 V AC
Frequency Converter
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
Enclosure IP20 (only)
A3
A3
A3
A3
A3
A3
A3
Output current
High overload 110% for 1 min
Continuous (3x525-550 V) [A]
2.1
2.7
3.9
4.9
6.1
9
11
Intermittent (3x525-550 V) [A]
2.3
3.0
4.3
5.4
6.7
9.9
12.1
Continuous kVA (3x551-690 V) [A]
1.6
2.2
3.2
4.5
5.5
7.5
10
Intermittent kVA (3x551-690 V) [A]
1.8
2.4
3.5
4.9
6.0
8.2
11
Continuous kVA 525 V AC
1.9
2.6
3.8
5.4
6.6
9
12
Continuous kVA 690 V AC
1.9
2.6
3.8
5.4
6.6
9
12
Max. input current
Continuous (3x525-550 V) [A]
1.9
2.4
3.5
4.4
5.5
8
10
Intermittent (3x525-550 V) [A]
2.1
2.6
3.8
8.4
6.0
8.8
11
Continuous kVA (3x551-690 V) [A]
1.4
2.0
2.9
4.0
4.9
6.7
9
Intermittent kVA (3x551-690 V) [A]
1.5
2.2
3.2
4.4
5.4
7.4
9.9
Additional specifications
IP20 max. cable cross section
5)
(mains, motor,
brake and load sharing) [mm
2
]/(AWG)
[0.2-4]/(24-10)
Estimated power loss at rated max. load [W]
4)
44
60
88
120
160
220
300
Weight, enclosure IP20 [kg]
6.6
6.6
6.6
6.6
6.6
6.6
6.6
Efficiency
4)
0.96
0.96
0.96
0.96
0.96
0.96
0.96
Table 9.7 Mains Supply 3x525-690 V AC IP20
General Specifications and ...
Design Guide
MG11BC02
Danfoss A/S © Rev. 06/2014 All rights reserved.
153
9