6.2.4 Fuse Tables
Enclosure
type
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A2
1.1-2.2
gG-10 (1.1-1.5)
gG-16 (2.2)
gG-25
PKZM0-25
25
A3
3.0-3.7
gG-16 (3)
gG-20 (3.7)
gG-32
PKZM0-25
25
B3
5.5-11
gG-25 (5.5-7.5)
gG-32 (11)
gG-63
PKZM4-50
50
B4
15-18
gG-50 (15)
gG-63 (18)
gG-125
NZMB1-A100
100
C3
22-30
gG-80 (22)
aR-125 (30)
gG-150 (22)
aR-160 (30)
NZMB2-A200
150
C4
37-45
aR-160 (37)
aR-200 (45)
aR-200 (37)
aR-250 (45)
NZMB2-A250
250
A4
1.1-2.2
gG-10 (1.1-1.5)
gG-16 (2.2)
gG-32
PKZM0-25
25
A5
0.25-3.7
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
gG-32
PKZM0-25
25
B1
5.5-11
gG-25 (5.5)
gG-32 (7.5-11)
gG-80
PKZM4-63
63
B2
15
gG-50
gG-100
NZMB1-A100
100
C1
18-30
gG-63 (18.5)
gG-80 (22)
gG-100 (30)
gG-160 (18.5-22)
aR-160 (30)
NZMB2-A200
160
C2
37-45
aR-160 (37)
aR-200 (45)
aR-200 (37)
aR-250 (45)
NZMB2-A250
250
Table 6.19 200-240 V, Enclosure Types A, B and C
Electrical Installation
Design Guide
96
Danfoss A/S © Rev. 06/2014 All rights reserved.
MG11BC02
6
6