No. Description
Warning
Alarm/
Trip
Alarm/Trip Lock
Parameter Reference
67
Option Configuration has Changed
X
68
Safe Stop
(X)
X
1)
5-19
69
Pwr. Card Temp
X
X
70
Illegal FC configuration
X
71
PTC 1 Safe Stop
X
X
1)
72
Dangerous Failure
X
1)
73
Safe Stop Auto Restart
76
Power Unit Setup
X
79
Illegal PS config
X
X
80
Drive Initialized to Default Value
X
91
Analog input 54 wrong settings
X
92
NoFlow
X
X
22-2*
93
Dry Pump
X
X
22-2*
94
End of Curve
X
X
22-5*
95
Broken Belt
X
X
22-6*
96
Start Delayed
X
22-7*
97
Stop Delayed
X
22-7*
98
Clock Fault
X
0-7*
201 Fire M was Active
202 Fire M Limits Exceeded
203 Missing Motor
204 Locked Rotor
243 Brake IGBT
X
X
244 Heatsink temp
X
X
X
245 Heatsink sensor
X
X
246 Pwr.card supply
X
X
247 Pwr.card temp
X
X
248 Illegal PS config
X
X
250 New spare parts
X
251 New Type Code
X
X
Table 9.34 Alarm/Warning Code List
(X) Dependent on parameter
1) Can not be Auto reset via 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip
will coast the motor and can be reset by pressing [Reset]
or make a reset by a digital input (parameter group 5-1*
[1]). The original event that caused an alarm cannot
damage the or cause dangerous conditions. A trip lock is
an action when an alarm occurs, which may cause damage
to or connected parts. A Trip Lock situation can only be
reset by a power cycling.
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 9.35 LED Indication