Enclosure
type
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A3
1.1
1.5
2.2
3
4
5.5
7.5
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
-
-
B2
11
15
18
22
30
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63 (30)
gG-63
gG-80 (30)
-
-
C2
37
45
55
75
gG-63 (37)
gG-80 (45)
gG-100 (55)
gG-125 (75)
gG-100 (37)
gG-125 (45)
gG-160 (55-75)
-
-
C3
45
55
gG-80
gG-100
gG-100
gG-125
-
-
Table 6.22 525-690 V, Enclosure Types A, B and C
Electrical Installation
Design Guide
98
Danfoss A/S © Rev. 06/2014 All rights reserved.
MG11BC02
6
6