Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
[kW]
1.1
KTS-R-5
JKS-5
JJS-6
FNQ-R-5
KTK-R-5
LP-CC-5
1.5-2.2
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3
KTS-R15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4
KTS-R20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11-15
KTS-R-35
JKS-35
JJS-35
-
-
-
18
KTS-R-45
JKS-45
JJS-45
-
-
-
22
KTS-R-50
JKS-50
JJS-50
-
-
-
30
KTS-R-60
JKS-60
JJS-60
-
-
-
37
KTS-R-80
JKS-80
JJS-80
-
-
-
45
KTS-R-100
JKS-100
JJS-100
-
-
-
55
KTS-R-125
JKS-125
JJS-125
-
-
-
75
KTS-R-150
JKS-150
JJS-150
-
-
-
90
KTS-R-175
JKS-175
JJS-175
-
-
-
Table 6.31 525-690 V, Enclosure Types A, B and C
Recommended max. fuse
Power
[kW]
Max.
prefuse
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273
J/JDDZ
Bussmann
E4273
T/JDDZ
SIBA
E180276
RK1/JDDZ
LittelFuse
E81895
RK1/JDDZ
Ferraz-
Shawmut
E163267/E2137
RK1/JDDZ
Ferraz-
Shawmut
E2137
J/HSJ
11-15
30 A
KTS-R-30
JKS-30
JKJS-30
5017906-030
KLS-R-030
A6K-30-R
HST-30
18.5
45 A
KTS-R-45
JKS-45
JJS-45
5014006-050
KLS-R-045
A6K-45-R
HST-45
30
60 A
KTS-R-60
JKS-60
JJS-60
5014006-063
KLS-R-060
A6K-60-R
HST-60
37
80 A
KTS-R-80
JKS-80
JJS-80
5014006-080
KLS-R-075
A6K-80-R
HST-80
45
90 A
KTS-R-90
JKS-90
JJS-90
5014006-100
KLS-R-090
A6K-90-R
HST-90
55
100 A
KTS-R-100
JKS-100
JJS-100
5014006-100
KLS-R-100
A6K-100-R
HST-100
75
125 A
KTS-R-125
JKS-125
JJS-125
2028220-125
KLS-150
A6K-125-R
HST-125
90
150 A
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-175
A6K-150-R
HST-150
Table 6.32 *525-690 V, Enclosure Types B and C
* UL compliance only 525-600 V
Electrical Installation
Design Guide
MG11BC02
Danfoss A/S © Rev. 06/2014 All rights reserved.
103
6
6