4.2.2 Start/Stop
Terminal 18 = Start/stop
parameter 5-10 Terminal 18 Digital
Input
[8] Start
.
Terminal 27 = No operation
parameter 5-12 Terminal 27
Digital Input
[0] No operation
(Default
[2] coast inverse
).
Parameter 5-10 Terminal 18 Digital Input
=
[8] Start
(default).
Parameter 5-12 Terminal 27 Digital Input
=
[2]
Coast inverse
(default).
12 13 18
37
130BA155.12
32
27
19
29
33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Illustration 4.1 Terminal 37: Available only with Safe Torque
Off (STO) Function
4.2.3 Pulse Start/Stop
Terminal 18 = Start/stop
parameter 5-10 Terminal 18 Digital
Input
[9] Latched start
.
Terminal 27= Stop
parameter 5-12 Terminal 27 Digital Input
[6] Stop inverse
.
Parameter 5-10 Terminal 18 Digital Input
=
[9]
Latched start
.
Parameter 5-12 Terminal 27 Digital Input
=
[6] Stop
inverse
.
12
13
18
37
130BA156.12
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start
Stop inverse
Safe Stop
Start (18)
Start (27)
Illustration 4.2 Terminal 37: Available Only with STO Function
Application Examples
VLT
®
Refrigeration Drive FC 103
92
Danfoss A/S © 08/2015 All rights reserved.
MG16G202
4
4