7.12.2 VLT
®
Relay Card MCB 105
The MCB 105 includes 3 pieces of SPDT contacts and fits into option slot B.
Electrical Data
Maximum terminal load (AC-1)
1)
(resistive load)
240 V AC 2 A
Maximum terminal load (AC-15)
1)
(inductive load
@
COS
φ
0.4)
240 V AC 0.2 A
Maximum terminal load (DC-1)
1)
(resistive load)
24 V DC 1 A
Maximum terminal load (DC-13)
1)
(inductive load)
24 V DC 0.1 A
Minimum terminal load (DC)
5 V 10 mA
Maximum switching rate at rated load/min load
6 minimum
-1
/20 s
-1
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately, the kit
includes:
•
Relay module MCB 105.
•
Enlarged LCP fixture and enlarged terminal cover.
•
Label for covering access to switches S201, S202,
and S801.
•
Cable strips for fastening cables to relay module.
2
130BA709.11
1
LABEL
Rem
ove jumpe
r to a
ctiva
te S
afe S
top
12
13
18
19
27
29
33
32
20
39
42
50
53
54
61
68
CAUTION:
SEE
MANU
AL / R
CD an
d high leak
age
curren
t
VOIR M
ANUAL
/ Fransk t
ekst
WARNING:
Stored
char
ge /
“Fransk
tekst” (4
min.)
LISTED 7
6x1 134
261
IND
USTRI
AL C
ONTR
OL EQ
UIP
MENT
SEE M
ANU
AL FOR PREFUS
E TUPE IN UL
APPLIC
ATIONS
T/C
: CIA
XXXPT5B20
BR1DBF00A
00
P/N : X
XXN11
00 S/N:
012815G432
IN: 3x380
-480V 50/60H
z 14.9A
OUT
: 3x0-Uin 0-
1000H
z 16.0A
11.1 kV
A
CHAS
IS/IP20
Tamb M
ax 45
C/113F
MADE IN DENM
ARK
9Ø
9Ø
Ø6
1
WARNING!
The label MUST be placed on the LCP frame as
shown (UL approved).
2 Relay card
Illustration 7.5 Enclosure Sizes A2, A3, and B3
2
130BA710.11
1
LABEL
Remove jump
er to activate S
afe Stop
13
12
18 19 27
32 38 2
28
42
39
53
50
5
616
9Ø
9Ø
DC- DC+
1
WARNING!
The label MUST be placed on the LCP frame as
shown (UL approved).
2 Relay card
Illustration 7.6 Enclosure Sizes A5, B1, B2, B4, C1, C2, C3, and
C4
WARNING
Warning Dual Supply
130BE040.10
Illustration 7.7 Warning Label Placed on Option
How to add the MCB 105:
1.
Disconnect power to the frequency converter.
2.
Disconnect power to the live part connections on
relay terminals.
3.
Remove the LCP, the terminal cover, and the LCP
fixture from the frequency converter.
4.
Fit the MCB 105 in slot B.
5.
Connect the control cables and fasten the cables
with the enclosed cable strips.
6.
Make sure that the length of the stripped wire is
correct (see
7.
Do not mix live parts (high voltage) with control
signals (PELV).
8.
Fit the enlarged LCP fixture and enlarged terminal
cover.
Specifications
VLT
®
Refrigeration Drive FC 103
136
Danfoss A/S © 08/2015 All rights reserved.
MG16G202
7
7