7.8.2 UL Compliance
3x200–240 V
Recommended maximum fuse
Power
[kW]
Bussmann
Type RK1
1)
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.1
KTN-R-10
JKS-10
JJN-10
FNQ-R-10
KTK-R-10
LP-CC-10
1.5
KTN-R-15
JKS-15
JJN-15
FNQ-R-15
KTK-R-15
LP-CC-15
2.2
KTN-R-20
JKS-20
JJN-20
FNQ-R-20
KTK-R-20
LP-CC-20
3.0
KTN-R-25
JKS-25
JJN-25
FNQ-R-25
KTK-R-25
LP-CC-25
3.7
KTN-R-30
JKS-30
JJN-30
FNQ-R-30
KTK-R-30
LP-CC-30
5.5/7.5
KTN-R-50
JKS-50
JJN-50
–
–
–
11
KTN-R-60
JKS-60
JJN-60
–
–
–
15
KTN-R-80
JKS-80
JJN-80
–
–
–
18.5–22
KTN-R-125
JKS-125
JJN-125
–
–
–
30
KTN-R-150
JKS-150
JJN-150
–
–
–
37
KTN-R-200
JKS-200
JJN-200
–
–
–
45
KTN-R-250
JKS-250
JJN-250
–
–
–
Table 7.12 3x200–240 V, Enclosure Types A, B, and C
Recommended maximum fuse
Power [kW]
SIBA
Type RK1
Littelfuse
Type RK1
Ferraz
Shawmut
Type CC
Ferraz
Shawmut
Type RK1
3)
Bussmann
Type JFHR2
2)
Littelfuse
JFHR2
Ferraz
Shawmut
JFHR2
4)
Ferraz
Shawmut
J
1.1
5017906-010
KLN-R-10
ATM-R-10
A2K-10-R
FWX-10
–
–
HSJ-10
1.5
5017906-016
KLN-R-15
ATM-R-15
A2K-15-R
FWX-15
–
–
HSJ-15
2.2
5017906-020
KLN-R-20
ATM-R-20
A2K-20-R
FWX-20
–
–
HSJ-20
3.0
5017906-025
KLN-R-25
ATM-R-25
A2K-25-R
FWX-25
–
–
HSJ-25
3.7
5012406-032
KLN-R-30
ATM-R-30
A2K-30-R
FWX-30
–
–
HSJ-30
5.5/7.5
5014006-050
KLN-R-50
–
A2K-50-R
FWX-50
–
–
HSJ-50
11
5014006-063
KLN-R-60
–
A2K-60-R
FWX-60
–
–
HSJ-60
15
5014006-080
KLN-R-80
–
A2K-80-R
FWX-80
–
–
HSJ-80
18.5–22
2028220-125
KLN-R-125
–
A2K-125-R
FWX-125
–
–
HSJ-125
30
2028220-150
KLN-R-150
–
A2K-150-R
FWX-150
L25S-150
A25X-150
HSJ-150
37
2028220-200
KLN-R-200
–
A2K-200-R
FWX-200
L25S-200
A25X-200
HSJ-200
45
2028220-250
KLN-R-250
–
A2K-250-R
FWX-250
L25S-250
A25X-250
HSJ-250
Table 7.13 3x200–240 V, Enclosure Types A, B, and C
1) KTS-fuses from Bussmann may substitute KTN for 240 V frequency converters.
2) FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
3) A6KR fuses from Ferraz Shawmut may substitute A2KR for 240 V frequency converters.
4) A50X fuses from Ferraz Shawmut may substitute A25X for 240 V frequency converters.
Specifications
Design Guide
MG16G202
Danfoss A/S © 08/2015 All rights reserved.
129
7
7
Содержание VLT FC 103
Страница 2: ......
Страница 159: ...Index Design Guide MG16G202 Danfoss A S 08 2015 All rights reserved 157...