Event 1 True (1)
Action 1 Select Preset (10)
Start
command
State 0
Stop
command
Event 4 False (0)
Action 4 No Action (1)
State 2
State 1
Event 2 On Reference (4)
Action 2 Start Timer (29)
Event 3 Time Out (30)
Action 3 Select Preset ref. (11)
130BA148.12
Illustration 4.5 SLC Application Example
4.3.1 Feedback
Parameters
FC
4-20 mA
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A 54
U - I
+
-
130BB675.10
Function
Setting
Parameter 6-22 Terminal
54 Low Current
4 mA*
Parameter 6-23 Terminal
54 High Current
20
mA*
Parameter 6-24 Terminal
54 Low Ref./Feedb.
Value
0*
Parameter 6-25 Terminal
54 High Ref./Feedb.
Value
50*
* = Default value
Notes/comments:
D IN 37 is an option.
Table 4.1 Analog Current Feedback Transducer
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A54
U - I
0 - 10V
+
-
130BB676.10
Function
Setting
Parameter 6-20 Ter
minal 54 Low
Voltage
0.07 V*
Parameter 6-21 Ter
minal 54 High
Voltage
10 V*
Parameter 6-24 Ter
minal 54 Low Ref./
Feedb. Value
0*
Parameter 6-25 Ter
minal 54 High Ref./
Feedb. Value
50*
* = Default value
Notes/comments:
D IN 37 is an option.
Table 4.2 Analog Voltage Feedback Transducer (3-wire)
Application Examples
Design Guide
MG16G202
Danfoss A/S © 08/2015 All rights reserved.
95
4
4