- To download data from the LCP to the control card, select
[2] All from LCP
.
Press [OK].
A progress bar shows the uploading or downloading process.
Press [Hand On] or [Auto On].
7.5.3 Restoring Factory Default Settings Using the Recommended Initialization
N O T I C E
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
To create a back-up, upload data to the LCP before initialization. See
7.5.2 Uploading and Downloading Parameter Settings
.
Press [Main Menu] twice to access parameters.
Go to
parameter 14-22 Operation Mode
and press [OK].
Parameter 14-22 Operation Mode
does not reset the following settings:
Running hours.
Serial communication options.
Personal menu settings.
Fault log, alarm log, and other monitoring functions.
Scroll to Initialization and press [OK].
Remove power to the unit and wait for the display to turn off.
Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal.
After
alarm 80, Drive initialized
appears, press [Reset].
7.5.4 Restoring Factory Default Settings Using Manual Initialization
N O T I C E
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
To create a back-up, upload data to the LCP before initialization. See
7.5.2 Uploading and Downloading Parameter Settings
.
Procedure
Remove power to the unit and wait for the display to turn off.
Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until
an audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
Parameter 15-00 Operating Hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Start-up takes slightly longer than normal.