Model Fuse P/N
Fuse size Rated cur-
rent [A]
Minimum pro-
spective SC cur-
rent of the grid
[kA]
Maximum fuse
rating F1 [A]
Minimum volt-
age rating [V]
Type F1
N560
Mersen NH4GG69V800 4
800
19
800
690
gG/gL
N630
Mersen NH4GG69V800 4
800
19
800
690
gG/gL
N710
ABB OFAA4AM1000
4
1000
25
1000
690
aM
N800
ABB OFAA4AM1000
4
1000
25
1000
690
aM
5.9.3 Recommended Fuse Ratings for UL Installation
The fuses and MCCBs contained in the enclosed drive are suitable for both short circuit and branch circuit protection. Use only these
fuses.
UL Approval is valid for maximum input voltage of 600 V. Per UL508A, the short-circuit current rating (SCCR) is as follows:
Enclosed drives with a fusible disconnect or fusible disconnect and contactor option have 65 kA SCCR at the rated voltage.
Enclosed drives with single switchgear (mains contactor only or non-fusible disconnect only option) have a 5 kA SCCR, but can
reach 65 kA if the recommended Class fuses are used upstream.
Enclosed drives with the MCCB option have a 65 kA interrupting rating for 380–480 V, and a 50 kA interrupting rating for525–
690 V.
The table values are calculated using correction factors for a 40 °C (104 °F) ambient operating condition and using cables with a
minimum insulation rating of 90 °C (194 °F).
Table 67: Recommended Fuse Ratings for UL Installation, 380–480 V
Model Fuse P/N (Mersen) Fuse P/N (Danfoss) Maximum current
[A]
Maximum fuse rat-
ing F1 [A]
Minimum voltage
rating [V]
Class F1
N110
A4J300
70CPE10965
300
300
500
Class J
N132
A4J350
70CPE10966
350
350
500
Class J
N160
A4J400
70CPE10522
400
400
500
Class J
N200
A4J500
70CPE10968
500
500
500
Class J
N250
A4J600
70CPE10523
600
600
500
Class J
N315
AABY750
70CPE10969
750
750
500
Class L
N355
A4BY800
70CPE10974
800
800
500
Class L
N400
A4BY1000
70CPE10975
1000
1000
500
Class L
N450
A4BY1000
70CPE10975
1000
1000
500
Class L
N500
A4BY1100
70CPE10976
1100
1100
500
Class L
N560
A4BY1200
70CPE10977
1200
1200
500
Class L
Table 68: Recommended Fuse Ratings for UL Installation, 525–600 V
Model Fuse P/N (Mersen) Fuse P/N (Danfoss) Maximum current
[A]
Maximum fuse rat-
ing F1 [A]
Minimum voltage
rating [V]
Class F1
N110
A4J175
70CPE10971
175
175
600
Class J
N132
A4J200
70CPE10521
200
200
600
Class J
N160
A4J250
70CPE10972
250
250
600
Class J
AQ357954340588en-000201 / 130R0881 | 91
Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide