8.1.6 Wiring Configuration: Start/Stop
Table 82: Wiring Configuration for Start/Stop Command with Safe Torque Off Option
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e
3
0
b
u
0
8
4
.1
0
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[Start]*
Parameter 5-12 Terminal 27 Digital Input
[0] No operation
Parameter 5-19 Terminal 37 Safe Stop
[1] Safe Stop Alarm
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27 Digital Input
is set to
[0] No operation
, a jumper wire to terminal
XD2.14 is not needed.
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Terminal 37 in the parameter title corresponds to terminal XD2.19 in the control compartment.
e
3
0
b
u
1
0
1
.1
0
Speed
Start/Stop (XD2.12)
Illustration 59: Wiring Configuration for Start/Stop Command with Safe Torque Off
Table 83: Wiring Configuration for Pulse Start/Stop
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e
3
0
b
u
0
8
5
.1
0
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[9] Latched Start
Parameter 5-12 Terminal 27 Digital Input
[6] Stop Inverse
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27 Digital Input
is set
[0] No operation
, a jumper wire to terminal
XD2.14 is not needed.
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
AQ357954340588en-000201 / 130R0881
110 | Danfoss A/S © 2020.09
Wiring Configuration Examples
VLT® Refrigeration Drive FC 103
Operating Guide