3.6.4 LCP Menu
Quick Menus
The
Quick Menus
mode provides a list of menus used to configure and operate the drive. Select the
Quick Menus
mode by pressing
the [Quick Menu] key. The resulting readout appears on the LCP display.
e
3
0
b
f2
4
1
.1
0
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q4 Smart Start
0.0% 0.00
Quick Menus
1(1)
Illustration 10: Quick Menu View
Q1 My Personal Menu
The
Personal Menu
is used to determine what is shown in the display area. Refer to
3.6.3 Local Control Panel (LCP)
. This menu can
also show up to 50 pre-programmed parameters. These 50 parameters are manually entered using
parameter 0-25 My Personal
Menu
.
Q2 Quick Setup
The parameters found in the
Q2 Quick Setup
contain basic system and motor data that are always necessary for configuring the
drive. See
7.2.4 Entering System Information
for the set-up procedures.
Q3 Function Setups
The parameters found in the
Q3 Function Setups
contain data for fan, compressor, and pump functions. This menu also includes
parameters for LCP display, digital preset speeds, scaling of analog references, closed-loop single-zone, and multizone applications.
Q4 Smart Setup
Q4 Smart Setup
guides the user through typical parameter settings used to configure 1 of the following 3 applications:
Mechanical brake.
Conveyor.
Pump/fan.
The [Info] key can be used to see help information for various selections, settings, and messages.
Q5 Changes Made
Select
Q5 Changes Mode
for information about:
The 10 most recent changes.
Changes made from default setting.
Q6 Loggings
Use
Q6 Loggings
for fault finding. To get information about the display line readout, select Loggings. The information is shown as
graphs. Only parameters selected in
parameter 0-20 Display Line 1.1 Small
through
parameter 0-24 Display Line 3 Large
can be viewed.
It is possible to store up to 120 samples in the memory for later reference.
Table 38: Logging Parameter Examples
Q6 Loggings
Parameter 0-20 Display Line 1.1 Small
Reference [%]
Parameter 0-21 Display Line 1.2 Small
Motor Current [A]
Parameter 0-22 Display Line 1.3 Small
Power [kW]
Parameter 0-23 Display Line 2 Large
Frequency
Parameter 0-24 Display Line 3 Large
kWh Counter
Main Menu
The
Main Menu
mode is used to:
AQ357954340588en-000201 / 130R0881
32 | Danfoss A/S © 2020.09
Product Overview
VLT® Refrigeration Drive FC 103