1.
•
•
1.
2.
3.
4.
Model Fuse P/N (Mersen) Fuse P/N (Danfoss) Maximum current
[A]
Maximum fuse rat-
ing F1 [A]
Minimum voltage
rating [V]
Class F1
N200
A4J350
70CPE10966
350
350
600
Class J
N250
A4J400
70CPE10522
400
400
600
Class J
N315
A4J500
70CPE10968
500
500
600
Class J
N400
A4J600
70CPE10523
600
600
600
Class J
N450
A4J600
70CPE10523
600
600
600
Class J
N500
A4BY650
70CPE110003
650
650
600
Class L
N560
AABY750
70CPE10969
750
750
600
Class L
N630
A4BY800
70CPE10974
800
800
600
Class L
N710
A4BY1000
70CPE10975
1000
1000
600
Class L
N800
A4BY1100
70CPE10976
1100
1100
600
Class L
5.10 Enabling Motor Operation
If the status line at the bottom of the LCP reads AUTO REMOTE COAST, the unit is ready to operate but is missing an input signal
from terminal XD2.14 in the control compartment. Digital input terminal XD2.14 is designed to receive a 24 V DC external interlock
command that allows the drive to operate when using factory default programming values.
N O T I C E
FACTORY-INSTALLED OPTIONAL EQUIPMENT
Do not remove factory-installed wiring to terminal XD2.14. If the drive does not run, refer to the documentation for the optional
equipment that is wired into terminal XD2.14.
Procedure
When no interlock device is used, use a push-in type jumper (WAGO 2002-433) between terminal XD2.11 and XD2.14 in the
control compartment. This wire provides an internal 24 V signal on terminal XD2.14. The drive is ready for operation.
5.11 Selecting the Voltage/Current Input Signal
The analog input terminals XD2.7 and XD2.8 in the control compartment allow setting of input signal to voltage (0–10 V) or current
(0/4–20 mA).
Terminal XD2.7: Speed reference signal in open loop (see
parameter 16-61 Terminal 53 Switch Setting
).
Terminal XD2.8: Feedback signal in closed loop (see
parameter 16-63 Terminal 54 Switch Setting
).
Procedure
Disconnect power to the drive.
Remove the LCP (local control panel).
Remove any optional equipment covering the switches.
Set switches A53 and A54 to select the signal type (U = voltage, I = current).
AQ357954340588en-000201 / 130R0881
92 | Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide