Type Designation
P30K
P37K
P45K
P55K
P75K
High/Normal Overload
1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output [kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP21
C1
C1
C1
C2
C2
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure IP55, IP66
C1
C1
C1
C2
C2
Output current
Continuous (380-440 V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 s overload)
(380-440 V) [A]
91.5
80.3
110
99
135
117
159
162
221
195
Continuous (441-500 V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 s overload)
(441-500 V) [A]
78
71.5
97.5
88
120
116
158
143
195
176
Continuous kVA (400 V) [kVA]
42.3
50.6
50.6
62.4
62.4
73.4
73.4
102
102
123
Continuous kVA (460 V) [kVA]
51.8
63.7
83.7
104
128
Max. input current
Continuous (380-440 V) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 s overload)
(380-440 V) [A]
82.5
72.6
99
90.2
123
106
144
146
200
177
Continuous (441-500 V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 s overload)
(441-500 V) [A]
70.5
64.9
88.5
80.3
110
105
143
130
177
160
Additional specifications
IP20 max. cable cross-section for
mains and motor [mm
2
] ([AWG])
35 (2)
50 (1)
50 (1)
150 (300 MCM)
150 (300 MCM)
IP20 max. cable cross-section for
brake and load sharing [mm
2
]
([AWG])
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
IP21, IP55, IP66 max. cable cross-
section for mains and motor [mm
2
]
([AWG])
50 (1)
50 (1)
50 (1)
150 (300 MCM)
150 (300MCM)
IP21, IP55, IP66 max. cable cross-
section for brake and load sharing
[mm
2
] ([AWG])
50 (1)
50 (1)
50 (1)
95 (3/0)
95 (3/0)
Max cable cross-section
4)
for
mains disconnect [mm
2
] ([AWG])
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Estimated power loss
at rated max. load [W]
3)
570
698
697
843
891
1083
1022
1384
1232
1474
Efficiency
2)
0.98
0.98
0.98
0.98
0.99
Table 6.6 Mains Supply 380-500 V (FC 302), 380-480 V (FC 301), P30K-P75K
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
62
MG33BF02 - Rev. 2013-12-20
6
6
Содержание VLT AutomationDrive FC 301
Страница 2: ......
Страница 199: ...Index VLT AutomationDrive FC 301 FC 302 Design Guide 0 25 75 kW MG33BF02 Rev 2013 12 20 197...