3.6.4 Control Structure in Flux Sensorless (FC 302 only)
+
_
+
_
130BA053.11
Ref.
Config. mode
P 1-00
P 7-20 Process feedback
1 source
P 7-22 Process feedback
2 source
Process
PID
P 4-11 Motor speed
low limit [RPM]
P 4-12 Motor speed
low limit [Hz]
P 4-14 Motor speed
high limit [Hz]
P 4-13 Motor speed
high limit [RPM]
Low
High
Ramp
P 3-**
+f max.
P 4-19
Max. output
freq.
Motor
controller
-f max.
Speed
PID
P 7-0*
Illustration 3.7 Control Structure in Flux Sensorless Open Loop and Closed Loop Configurations
See
Active/Inactive Parameters in Different Drive Control Modes
in the
Programming Guide
for an overview of which control
configuration is available, depending on selection of AC motor or PM Non salient motor. In the shown configuration,
1-01 Motor Control Principle
is set to
[2] Flux sensorless
and
1-00 Configuration Mode
is set to
[0] Speed open loop
. The
resulting reference from the reference handling system is fed through the ramp and speed limitations as determined by the
parameter settings indicated.
An estimated speed feedback is generated to the Speed PID to control the output frequency.
The Speed PID must be set with its P,I, and D parameters (parameter group
7-0* Speed PID control
).
Select
[3] Process
in
1-00 Configuration Mode
to use the process PID control for closed loop control of i.e. speed or pressure
in the controlled application. The Process PID parameters are found in parameter group
7-2* Process Ctrl. Feedb
and
7-3*
Process PID Ctrl
.
Basic Operating Principles
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20
21
3
3