NOTICE
Make a selection in
8-56 Preset Reference Select
to define
how Bit 00/01 gates with the corresponding function on
the digital inputs.
Bit 02, DC brake
Bit 02 = ’0’ leads to DC braking and stop. Set braking
current and duration in
2-01 DC Brake Current
and
2-02 DC
Braking Time
.
Bit 02 = ’1’ leads to ramping.
Bit 03, Coasting
Bit 03 = ’0’: The frequency converter immediately "lets go"
of the motor, (the output transistors are "shut off") and it
coasts to a standstill.
Bit 03 = ’1’: The frequency converter starts the motor, if
the other starting conditions are met.
Make a selection in
8-50 Coasting Select
to define how Bit
03 gates with the corresponding function on a digital
input.
Bit 04, Quick stop
Bit 04 = ’0’: Makes the motor speed ramp down to stop
(set in
3-81 Quick Stop Ramp Time
).
Bit 05, Hold output frequency
Bit 05 = ’0’: The present output frequency (in Hz) freezes.
Change the frozen output frequency only with the digital
inputs (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33
Digital Input
) programmed to
Speed up
and
Slow down
.
NOTICE
If Freeze output is active, the frequency converter can
only be stopped by the following:
•
Bit 03 Coasting stop
•
Bit 02 DC braking
•
Digital input (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33 Digital Input
) programmed to
DC braking
,
Coasting stop
, or
Reset
and
coasting
stop
.
Bit 06, Ramp stop/start
Bit 06 = ’0’: Causes a stop and makes the motor speed
ramp down to stop via the selected ramp down parameter.
Bit 06 = ’1’: Permits the frequency converter to start the
motor, if the other starting conditions are met.
Make a selection in
8-53 Start Select
to define how Bit 06
Ramp stop/start gates with the corresponding function on
a digital input.
Bit 07, Reset
Bit 07 = ’0’: No reset. Bit 07 = ’1’: Resets a trip. Reset is
activated on the signal’s leading edge, i.e. when changing
from logic ’0’ to logic ’1’.
Bit 08, Jog
Bit 08 = ’1’: The output frequency is determined by
3-19 Jog Speed [RPM]
.
Bit 09, Selection of ramp 1/2
Bit 09 = "0": Ramp 1 is active (
3-41 Ramp 1 Ramp Up Time
to
3-42 Ramp 1 Ramp Down Time
). Bit 09 = "1": Ramp 2
(
3-51 Ramp 2 Ramp Up Time
to
3-52 Ramp 2 Ramp Down
Time
) is active.
Bit 10, Data not valid/Data valid
Tells the frequency converter whether to use or ignore the
control word.
Bit 10 = ’0’: The control word is ignored. Bit 10 = ’1’: The
control word is used. This function is relevant because the
telegram always contains the control word, regardless of
the telegram type. Turn off the control word, if it should
not be used when updating or reading parameters.
Bit 11, Relay 01
Bit 11 = "0": Relay not activated.
Bit 11 = "1": Relay 01 activated provided that
Control word
bit 11
is selected in
5-40 Function Relay
.
Bit 12, Relay 04
Bit 12 = "0": Relay 04 is not activated.
Bit 12 = "1": Relay 04 is activated provided that
Control
word bit 12
is selected in
5-40 Function Relay
.
Bit 13/14, Selection of set-up
Use bits 13 and 14 to select from the 4 menu set-ups
according to
.
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
Table 12.22 4 Menu Set-ups
The function is only possible when
Multi Set-Ups
is selected
in
0-10 Active Set-up
.
Make a selection in
8-55 Set-up Select
to define how Bit
13/14 gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15 = ’0’: No reversing.
Bit 15 = ’1’: Reversing. In the default setting, reversing is
set to digital in
8-54 Reversing Select
. Bit 15 causes
reversing only when Ser. communication, Logic or or Logic
and is selected.
RS-485 Installation and Set...