Digital input - terminal X30/1-4
Number of digital inputs
3
Terminal number
X30.2, X30.3, X30.4
Logic
PNP or NPN
Voltage level
0-24 V DC
Voltage level, logic'0' PNP (GND = 0 V)
< 5 V DC
Voltage level, logic'1' PNP (GND = 0 V)
> 10 V DC
Voltage level, logic '0' NPN (GND = 24 V)
< 14 V DC
Voltage level, logic '1' NPN (GND = 24 V)
> 19 V DC
Maximum voltage on input
28 V continous
Pulse frequency range
0-110 kHz
Duty cycle, min. pulse width
4.5 ms
Input impedance
> 2 kΩ
Analog input - terminal X30/11, 12
Number of analog inputs
2
Terminal number
X30.11, X30.12
Modes
Voltage
Voltage level
0-10 V
Input impedance
> 10 kΩ
Max. voltage
20 V
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Max. error 0.5% of full scale
Bandwidth
FC 301: 20 Hz/ FC 302: 100 Hz
Digital outputs - terminal X30/6, 7
Number of digital outputs
2
Terminal number
X30.6, X30.7
Voltage level at digital/frequency output
0-24 V
Max. output current
40 mA
Max. load
≥ 600 Ω
Max. capacitive load
< 10 nF
Minimum output frequency
0 Hz
Maximum output frequency
≤ 32 kHz
Accuracy of frequency output
Max. error: 0.1 % of full scale
Analog output - terminal X30/8
Number of analog outputs
1
Terminal number
X30.8
Current range at analog output
0-20 mA
Max. load GND - analog output
500 Ω
Accuracy on analog output
Max. error: 0.5 % of full scale
Resolution on analog output
12 bit