Recommended max. fuse
Power
[kW]
SIBA
Type RK1
Littel fuse
Type RK1
Ferraz-
Shawmut
Type CC
Ferraz-
Shawmut
Type RK1
0.37-1.1
5017906-006
KLS-R-6
ATM-R-6
A6K-6-R
1.5-2.2
5017906-010
KLS-R-10
ATM-R-10
A6K-10-R
3
5017906-016
KLS-R-15
ATM-R-15
A6K-15-R
4
5017906-020
KLS-R-20
ATM-R-20
A6K-20-R
5.5
5017906-025
KLS-R-25
ATM-R-25
A6K-25-R
7.5
5012406-032
KLS-R-30
ATM-R-30
A6K-30-R
11
5014006-040
KLS-R-40
-
A6K-40-R
15
5014006-050
KLS-R-50
-
A6K-50-R
18
5014006-063
KLS-R-60
-
A6K-60-R
22
2028220-100
KLS-R-80
-
A6K-80-R
30
2028220-125
KLS-R-100
-
A6K-100-R
37
2028220-125
KLS-R-125
-
A6K-125-R
45
2028220-160
KLS-R-150
-
A6K-150-R
55
2028220-200
KLS-R-200
-
A6K-200-R
75
2028220-250
KLS-R-250
-
A6K-250-R
Table 9.11 380-500 V, Enclosure Types A, B and C