9.7 Additional Motor Information
9.7.1 Motor Cable
All types of 3-phase asynchronous standard motors can be
used with a frequency converter unit. The factory setting is
for clockwise rotation with the frequency converter output
connected as follows.
175HA036.11
U
1
V
1
W
1
96
97
98
FC
Motor
U
2
V
2
W
2
U
1
V
1
W
1
96
97
98
FC
Motor
U
2
V
2
W
2
Illustration 9.49 Terminal Connection for Clockwise and
Counter-clockwise Rotation
The direction of rotation can be changed by switching 2
phases in the motor cable or by changing the setting of
4-10 Motor Speed Direction
.
Motor rotation check can be performed using
1-28 Motor
Rotation Check
and following the steps shown in the
display.
9.7.2 Connection of Multiple Motors
NOTICE
Problems may arise at start and at low RPM values if
motor sizes are widely different because small motors'
relatively high ohmic resistance in the stator calls for a
higher voltage at start and at low RPM values.
The frequency converter can control several parallel-
connected motors. When using parallel motor connection
observe the following:
•
VCC
+
mode may be used in some applications.
•
The total current consumption of the motors
must not exceed the rated output current I
INV
for
the frequency converter.
•
Do not use common joint connection for long
cable lengths, see
.
•
The total motor cable length specified in
, is valid as long as the parallel cables are
kept short (less than 10 m each), see
and
.
•
Consider voltage drop across the motor cable,
see
.
•
For long parallel cables, use LC filter, see
•
For long cables without parallel connection, see
NOTICE
When motors are connected in parallel,
1-02 Flux Motor
Feedback Source
cannot be used, and
1-01 Motor Control
Principle
must be set to
[0] U/f
.
130BD774.10
Illustration 9.50 Common Joint Connection for Short Cable
Lengths
Electrical Installation
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
140
MG33BF02 - Rev. 2013-12-20
9
9
Содержание VLT AutomationDrive FC 301
Страница 2: ......
Страница 199: ...Index VLT AutomationDrive FC 301 FC 302 Design Guide 0 25 75 kW MG33BF02 Rev 2013 12 20 197...