11.2.8.1 Electrical and Mechanical Specifications
Analogue Input
Number of analogue inputs
1
Format
0–20 mA or 4–20 mA
Wires
2
Input impedance
<200
Ω
Sample rate
1 kHz
3rd order filter
100 Hz at 3 dB
The option is able to supply the analogue sensor with 24 V
DC (terminal 1).
Temperature Sensor Input
Number of analogue inputs supporting PT100/1000
3
Signal type
PT100/1000
Connection
PT 100 2 or 3 wire/PT1000 2 or 3 wire
Frequency PT100 and PT1000 input
1 Hz for each channel
Resolution
10 bit
Temperature range
-50–204
°
C
-58–399
°
F
Galvanic Isolation
The sensors to be connected are expected to be galvanically isolated from the mains voltage
level
IEC 61800-5-1 and UL508C
Cabling
Maximum signal cable length
500 m
11.2.8.2 Electrical Wiring
MCB 114
Sensor Input
Option B
SW. ver. xx.xx
Code No. 130B1272
VDD
I IN
GND
TEMP
1
WIRE
1
GND
TEMP
2
WIRE
2
GND
TEMP
3
WIRE
3
GND
X48/
1
2
3
4
5
6
7
8
9 10 11 12
4-20mA
2 or 3
wire
2 or 3
wire
2 or 3
wire
2 or 3
wire
1
3
0
BB3
2
6
.1
0
Terminal
Name
Function
1
VDD
24 V DC to supply 4-20 mA
sensor
2
I in
4-20 mA input
3
GND
Analog input GND
4, 7, 10
Temp 1, 2, 3
Temperature input
5, 8, 11
Wire 1, 2, 3
3
rd
wire input if 3 wire
sensors are used
6, 9, 12
GND
Temp. input GND
Illustration 11.18 MCB 114
Options and Accessories
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
164
MG33BF02 - Rev. 2013-12-20