525 - 690 Volt
VLT Type
P400
P500
P560
Max. Input Current [A]
550
413
504
504
574
574
607
Max. Input Current [A]
575
395
482
482
549
549
607
Max. Input Current [A]
690
395
482
482
549
549
607
Max. external pre-fuses
1)
[A]
700
900
900
Soft Charge Fuses
2)
AC [A]
(qty)
20 (3)
SMPS fuse
3)
[A]
4
AC Fan fuse
3)
[A]
4
15
Supply Voltage [V]
3 Phase, 525-690 ± 10%
Supply Frequency [Hz]
50/ 60
Power Factor
>0.90 for 525 V
Efficiency
0.98
Power loss at rated max. load (690 V)
High Overload (150%) [W]
5818
7671
8715
Normal Overload (110%) [W]
7249
8727
9673
Enclosure
IP00, IP21/ NEMA 1 & IP54/ NEMA 12
Vibration Test [g]
0.7
Relative Humidity [%]
93%, +2%, -3% (IEC 68-2-3)
Ambient Temperature [de-
grees C]
-10 Deg C to 40 Deg C continuously, period-
ically at +45 degrees C
-25 Deg C to +65/ 70 Deg C for storage/
transport
Adjustable Frequency Drive
Protection
Ground and short-circuit protection
Weight
5)
IP00/ Chassis [kg]
221
236
277
IP21/ NEMA 1 [kg]
263
272
313
IP54/ NEMA 12 [kg]
263
272
313
1) Bussman 170M6000 series. See fuse chart
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no loadsharing
VLT
®
Automation Drive FC 300
Operating Instructions High Power
5. General Specifications
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
121