525 - 690 Volt
VLT Type
P200
P250
P315
P355
Output current
[VAC]
HO
NO
HO
NO
HO
NO
HO
NO
Continuous (100/ 100%) [A]
550
253 303 303 360 360 418
395
470
Intermittent (150/ 110%) [A]
550
380 333 455 396 540 460
593
517
Continuous (100/ 100%) [A]
575/ 690 242 290 290 344 344 400
380
450
Intermittent (150/ 110%) [A]
575/ 690 363 319 435 378 516 440
570
495
Output kVA
Continuous (100/ 100%) [kVA]
550
241 289 289 343 343 398
376
448
Intermittent (150/ 110%) [kVA]
550
362 318 433 377 514 438
564
493
Continuous (100/ 100%) [kVA]
575
241 289 289 343 343 398
378
448
Intermittent (150/ 110%) [kVA]
575
362 318 433 377 514 438
568
493
Continuous (100/ 100%) [kVA]
690
289 347 347 411 411 478
454
538
Intermittent (150/ 110%) [kVA]
690
434 381 520 452 617 526
681
592
Typical Shaft Output
High Overload (150%) [kW]
550
160
200
250
315
Normal Overload (110%) [kW]
550
200
250
315
355
High Overload (150%) [HP]
575
250
300
350
400
Normal Overload (110%) [HP]
575
300
350
400
450
High Overload (150%) [kW]
690
200
250
315
355
Normal Overload (110%) [kW]
690
250
315
400
450
Max. Motor Cable Length
500 feet (150 m) shielded, 1000 feet (300 m) un-
shielded
Output Voltage [%]
0-100% of the AC line voltage
Output Frequency [Hz]
0-200
0-150
Rated Motor Voltage [V]
550/
575/
690
Rated Motor Frequency [Hz]
50/60
Thermal protection during
operation
ETR for motor (Class 20)
Thermal protection during
operation
110
110
110
85
Switching on the Output
Unlimited
Ramp times [sec]
0.01 - 3600
5. General Specifications
VLT
®
Automation Drive FC 300
Operating Instructions High Power
118