380 - 500 Volt
VLT Type
P110
P132
P160
P200
Max. Input Current [A]
400
204 251 251 304 304 381 381 463
Max. Input Current [A]
460/ 500
183 231 231 291 291 348 348 427
Max. external pre-fuses
1)
[A]
350
400
500
600
Soft Charge Fuses
2)
AC [A]
(qty)
20
(3)
SMPS fuse
3)
[A]
4
AC Fan fuse
3)
[A]
4
Supply Voltage [V]
3 Phase, 380-500 ± 10%
Supply Frequency [Hz]
50/
60
Power Factor
greater than 0.90
Efficiency
0.98
Power loss at rated max. load (400V)
High Overload (150%) [W]
2995
3425
3910
4625
Normal Overload (110%) [W]
3782
4213
5119
5893
Enclosure
IP00, IP21/ NEMA 1 & IP54/ NEMA 12
Vibration Test [g]
0.7
Relative Humidity [%]
93%, +2%, -3% (IEC 68-2-3)
Ambient Temperature [de-
grees C]
-10 Deg C to 40 Deg C continuously, periodi-
cally at +45 degrees C
-25 Deg C to +65/ 70 Deg C for storage/
transport
Adjustable Frequency Drive
Protection
Ground and short-circuit protection
Weight
5)
IP00/ Chassis [kg]
90.5
111.8
122.9
137.7
IP21/ NEMA 1 [kg]
104.1
125.4
136.3
151.3
IP54/ NEMA 12 [kg]
104.1
125.4
136.3
151.3
1) Bussman 170M6000 series. See fuse chart
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no loadshare
VLT
®
Automation Drive FC 300
Operating Instructions High Power
5. General Specifications
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
113