![Danfoss VLT Automation Drive FC 300 Скачать руководство пользователя страница 117](http://html1.mh-extra.com/html/danfoss/vlt-automation-drive-fc-300/vlt-automation-drive-fc-300_operating-instructions-manual_3441740117.webp)
525 - 690 Volt
VLT Type
P110
P132
P160
Max. Input Current [A]
550
130
158
158
198
198
245
Max. Input Current [A]
575
124
151
151
189
189
234
Max. Input Current [A]
690
128
155
155
197
197
240
Max. external pre-fuses
1)
[A]
225
250
350
Soft Charge Fuses
2)
AC [A] (qty)
20 (3)
SMPS fuse
3)
[A]
4
AC Fan fuse
3)
[A]
4
Supply Voltage [V]
3 Phase, 525-690 ± 10%
Supply Frequency [Hz]
50/ 60
Power Factor
>0.90 for 525 V, >0.85 for 690 V
Efficiency
0.98
Power loss at rated max. load (690 V)
High Overload (150%) [W]
2665
2953
3451
Normal Overload (110%) [W]
3114
3612
4293
Enclosure
IP00, IP21/ NEMA 1 & IP54/ NEMA 12
Vibration Test [g]
0.7
Relative Humidity [%]
93%, +2%, -3% (IEC 68-2-3)
Ambient Temperature [degrees
C]
-10 Deg C to 40 Deg C continuously, pe-
riodically at +45 degrees C
-25 Deg C to +65/ 70 Deg C for storage/
transport
Adjustable Frequency Drive Pro-
tection
Ground and short-circuit protection
Weight
5)
IP00/ Chassis [kg]
81.9
90.5
111.8
IP21/ NEMA 1 [kg]
95.5
104.1
125.4
IP54/ NEMA 12 [kg]
95.5
104.1
125.4
1) Bussman 170M6000 series. See fuse chart
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no loadsharing
VLT
®
Automation Drive FC 300
Operating Instructions High Power
5. General Specifications
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
117
5