Mains Supply 3 x 380 - 480 VAC
P500
P560
P630
P710
P800
P1M0
Typical Shaft output
at 400 V [kW]
500
560
630
710
800
1000
Typical Shaft output
at 460 V [HP]
650
750
900
1000
1200
1350
Enclosure IP21, 54
without/ with op-
tions cabinet
F1/F3
F1/F3
F1/F3
F1/F3
F2/F4
F2/F4
Output current
Continuous
(at 400 V) [A]
880
990
1120
1260
1460
1720
Intermittent (60 sec
overload)
(at 400 V) [A]
968
1089
1232
1386
1606
1892
Continuous
(at 460/ 480 V) [A]
780
890
1050
1160
1380
1530
Intermittent (60 sec
overload)
(at 460/ 480 V) [A]
858
979
1155
1276
1518
1683
Continuous KVA
(at 400 V) [KVA]
610
686
776
873
1012
1192
Continuous KVA
(at 460 V) [KVA]
621
709
837
924
1100
1219
Max. input current
Continuous
(at 400 V ) [A]
857
964
1090
1227
1422
1675
Continuous (at 460/
480 V) [A]
759
867
1022
1129
1344
1490
Max. cable size,mo-
tor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable
size,mains [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,
loadsharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size,
brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-
fuses [A]
1
1600
2000
2500
Est. power loss at
rated max. load
[W]
4)
, 400 V, F1 &
F2
10647
12338
13201
15436
18084
20358
Est. power loss at
rated max. load [W]
4)
, 460 V, F1 & F2
9414
11006
12353
14041
17137
17752
Max added losses of
A1 RFI, Circuit
Breaker or Discon-
nect, & Contactor,
F3 & F4
963
1054
1093
1230
2280
2541
Max Panel Options
Losses
400
Weight,
enclosure IP21, IP
54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight Rectifier
Module [kg]
102
102
102
102
136
136
Weight Inverter
Module [kg]
102
102
102
136
102
102
Efficiency
4)
0.98
Output
frequency
0-600
Hz
Heatsink overtemp.
trip
95 °C
Power card ambient
trip
68 °C
VLT AQUA High Power Operation Instructions
6 General Specifications
MG.20.P3.02 - VLT
®
is a registered Danfoss trademark
177