Mains Supply 3 x 525- 690 VAC
P315
P400
P450
Typical Shaft output at 550 V
[kW]
250
315
355
Typical Shaft output at 575 V
[HP]
350
400
450
Typical Shaft output at 690 V
[kW]
315
400
450
Enclosure IP21
D2
D2
E1
Enclosure
IP54
D2
D2
E1
Enclosure IP00
D4
D4
E2
Output current
Continuous
(at 550 V) [A]
360
418
470
Intermittent (60 sec overload)
(at 550 V) [A]
396
460
517
Continuous
(at 575/ 690 V) [A]
344
400
450
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
378
440
495
Continuous KVA
(at 550 V) [KVA]
343
398
448
Continuous KVA
(at 575 V) [KVA]
343
398
448
Continuous KVA
(at 690 V) [KVA]
411
478
538
Max. input current
Continuous
(at 550 V ) [A]
355
408
453
Continuous
(at 575 V) [A]
339
390
434
Continuous
(at 690 V) [A]
352
400
434
Max. cable size, mains, motor
and load share [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
4 x 240
(4 x 500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
500
550
700
Estimated power loss
at rated max. load [W]
4)
, 575
V
5493
5852
6132
Estimated power loss
at rated max. load [W]
4)
, 690
V
5821
6149
6440
Weight,
enclosure IP21, IP 54 [kg]
151
165
263
Weight,
enclosure IP00 [kg]
138
151
221
Efficiency
4)
0.98
Output
frequency
0 - 600 Hz
0 - 500 Hz
0 - 500 Hz
Heatsink overtemp. trip
110 °C
110 °C
85 °C
Power card ambient trip
60 °C
60 °C
68 °C
6 General Specifications
VLT AQUA High Power Operation Instructions
180
MG.20.P3.02 - VLT
®