22-80 Flow Compensation
Option:
Function:
[0] *
Disabled
[0]
Disabled
: Set-Point compensation not active.
[1]
Enabled
[1]
Enabled
:Set-Point compensation is active. Enabling this parameter allows the Flow Compensated
Setpoint operation.
22-81 Square-linear Curve Approximation
Range:
Function:
100 %*
[0 - 100 %]
Example 1:
Adjustment of this parameter allows the shape of the control curve to be adjusted.
0 = Linear
100% = Ideal shape (theoretical).
NB!
Please note: Not visible when running in cascade.