4.1.8 Read-out and Programming of Indexed Parameters
Parameters are indexed when placed in a rolling stack.
par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
contain a fault log which can be read out. Choose a parameter, press [OK], and use the
up/down navigation keys to scroll through the value log.
Use par. 3-10
as another example:
Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed values. To change the parameter value,
select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [Cancel] to abort.
Press [Back] to leave the parameter.
4.1.9 Tips and tricks
*
For the majority of water and wastewater applications the Quick Menu, Quick Setup and Function Setups provides the simplest
and quickest access to all the typical parameters required.
*
Whenever possible, performing an AMA, will ensure best shaft performance
*
Contrast of the display can be adjusted by pressing [Status] and [
▲
] for darker display or by pressing [Status] and [
▼
] for
brighter dispaly
*
Under [Quick Menu] and [Changes Made] all parameters that have been changed from factory settings are displayed
*
Press and hold [Main Menu] key for 3 seconds for access to any parameter
*
For service purposes it is recommended to copy all parameters to the LCP, see par 0-50 for further information
Table 4.1: Tips and tricks
4.1.10 Quick Transfer of Parameter Settings when using GLCP
Once the set-up of a frequency converter is complete, it is recommended to store (backup) the parameter settings in the GLCP or on a PC via MCT 10
Set-up Software Tool.
NB!
Stop the motor before performing any of these operations.
Data storage in LCP:
1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
All parameter settings are now stored in the GLCP indicated by the progress bar. When 100% is reached, press [OK].
The GLCP can now be connected to another frequency converter and the parameter settings copied to this frequency converter.
Data transfer from LCP to Frequency converter:
1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press
[OK].