3-10 Preset Reference
Array [8]
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
Enter up to eight different preset references (0-7) in this parameter, using array programming. The
preset reference is stated as a percentage of the value Ref
MAX
, for
closed loop see par. 20-14
Maximum Reference/Feedb.
). When using preset references, select Pre-
set ref. bit 0 / 1 / 2 [16], [17] or [18] for the corresponding digital inputs in parameter group 5-1*
Digital Inputs.
3-41 Ramp 1 Ramp Up Time
Range:
Function:
10.00 s*
[1.00 - 3600.00 s]
Enter the ramp-up time, i.e. the acceleration time from 0 RPM to par. 1-25
.
Choose a ramp-up time such that the output current does not exceed the current limit in par.
4-18
Current Limit
during ramping. See ramp-down time in par. 3-42
.
par
.3
−
41 =
tacc
×
nnorm
par
.1
−
25
ref
rpm
s
3-42 Ramp 1 Ramp Down Time
Range:
Function:
20.00 s*
[1.00 - 3600.00 s]
Enter the ramp-down time, i.e. the deceleration time from par. 1-25
to 0 RPM.
Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative
operation of the motor, and such that the generated current does not exceed the current limit set
in par. 4-18
Current Limit
. See ramp-up time in par. 3-41
par
.3
−
42 =
tdec
×
nnorm
par
.1
−
25
ref
rpm
s
3-84 Initial Ramp Time
Range:
Function:
0 s*
[0 – 60 s]
Enter the initial ramp up time from zero speed to Motor Speed Low Limit, par. 4-11 or 4-12. Sub-
mersible deep well pumps can be damaged by running below minimum speed. A fast ramp time
below minimum pump speed is recommended. This parameter may be applied as a fast ramp rate
from zero speed to Motor Speed Low Limit.