380–480 V
Enclosure
Power [kW]
Recommended
fuse size
Recommended
max. fuse
Recommended circuit
breaker
Moeller
Max. trip level [A]
A2
1.5–5 [1.1–4.0]
gG-10 (0.5–4 [0.37–3])
gG-16 (5 [4])
gG-25
PKZM0-25
25
A3
7.5–10 [5.5–7.5]
gG-16
gG-32
PKZM0-25
25
A4
1.5–5 [1.1–4.0]
gG-10 (0.5–4 [0.37–3])
gG-16 (5 [4])
gG-32
PKZM0-25
25
A5
1.5–10 [1.1–7.5]
gG-10 (0.5–4 [0.37–3])
gG-16 (5–10 [4–7.5])
gG-32
PKZM0-25
25
B1
15–25 [11–18.5]
gG-40
gG-80
PKZM4-63
63
B2
30–40 [22–30]
gG-50 (25 [18.5])
gG-63 (30 [22])
gG-100
NZMB1-A100
3.94 [100]
B3
15–25 [11–18]
gG-40
gG-63
PKZM4-50
50
B4
30–50 [22–37]
gG-50 (25 [18.5])
gG-63 (30 [22])
gG-80 (40 [30])
gG-125
NZMB1-A100
100
C1
50–75 [37–55]
gG-80 (40 [30])
gG-100 (50 [37])
gG-160 (60 [45])
gG-160
NZMB2-A200
160
C2
100–125 [75–90]
aR-200 (75 [55])
aR-250 (100 [75])
aR-250
NZMB2-A250
250
C3
60–75 [45–55]
gG-100 (50 [37])
gG-160 (60 [45])
gG-150 (50 [37])
gG-160 (60 [45])
NZMB2-A200
150
C4
100–125 [75–90]
aR-200 (75 [55])
aR-250 (100 [75])
aR-250
NZMB2-A250
250
Table 8.14 380–480 V, Enclosure Types A, B and C
Specifications
VLT
®
AQUA Drive FC 202
68