![background image](http://html1.mh-extra.com/html/danfoss/vlt-aqua-drive-fc-202/vlt-aqua-drive-fc-202_instruction-manual_3505209017.webp)
For EMC-compliant installation
•
Establish electrical contact between cable shield
and adjustable frequency drive enclosure by
using metal cable connectors or by using the
clamps provided on the equipment (see
and
•
Use high-strand wire to reduce electrical
interference.
•
Do not use pigtails.
NOTICE!
POTENTIAL EQUALIZATION!
Risk of electrical interference, when the ground potential
between the adjustable frequency drive and the system
is different. Install equalizing cables between the system
components. Recommended cable cross-section: AWG 6
[16 mm
2
].
Electrical Installation
Instruction Manual
MG20MA22
Danfoss A/S © 10/2014 All rights reserved.
15
4
4
Содержание VLT AQUA Drive FC 202
Страница 2: ......
Страница 5: ...Index 83 Contents Instruction Manual MG20MA22 Danfoss A S 10 2014 All rights reserved...