5.3.3 Parameter Settings
Establishing the correct programming for applications
often requires setting functions in several related
parameters. Details for parameters are provided in
chapter 9.2 Parameter Menu Structure
.
Programming data are stored internally in the adjustable
frequency drive.
•
For backup, upload data into the LCP memory
•
To download data to another adjustable
frequency drive, connect the LCP to that unit and
download the stored settings
•
Restoring factory default settings does not
change data stored in the LCP memory
5.3.4 Uploading/Downloading Data to/from
the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Go to [Main Menu]
0-50 LCP Copy
and Press [OK].
3.
Select
[1] All to LCP
to upload data to LCP or
select
[2] All from LCP
to download data from the
LCP.
4.
Press [OK]. A progress bar shows the uploading
or downloading process.
5.
Press [Hand On] or [Auto On] to return to normal
operation.
5.3.5 Changing Parameter Settings
View changes
Quick Menu Q5 - Changes Made
lists all parameters
changed from default settings.
•
The list shows only parameters which have been
changed in the current edit set-up.
•
Parameters which have been reset to default
values are not listed.
•
The message 'Empty' indicates that no
parameters have been changed.
Changing settings
Parameter settings can be accessed and changed from the
[Quick Menu] or from the [Main Menu]. The [Quick Menu]
only gives access to a limited number of parameters.
1.
Press [Quick Menu] or [Main Menu] on the LCP.
2.
Press [
▲
] [
▼
] to browse through the parameter
groups, press [OK] to select a parameter group.
3.
Press [
▲
] [
▼
] to browse through the parameters,
press [OK] to select a parameter.
4.
Press [
▲
] [
▼
] to change the value of a parameter
setting.
5.
Press [
◄
] [
►
] to shift digit when a decimal
parameter is in the editing state.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter “Status”, or
press [Main Menu] once to enter “Main Menu”.
5.3.6 Restoring Default Settings
NOTICE!
Risk of losing programming, motor data, localization,
and monitoring records by restoration of default
settings. To provide a backup, upload data to the LCP
before initialization.
Restoring the default parameter settings is done by initiali-
zation of the adjustable frequency drive. Initialization is
carried out through
14-22 Operation Mode
(recommended)
or manually.
•
Initialization using
14-22 Operation Mode
does not
reset adjustable frequency drive settings such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure, via
14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
14-22 Operation Mode
and press [OK].
3.
Scroll to
Initialization
and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Commissioning