7.5 Troubleshooting
Symptom
Possible cause
Test
Solution
Display
dark/No
function
Missing input power
See
Check the input power source.
Missing or open fuses or circuit
breaker tripped
See open fuses and tripped circuit breaker
in this table for possible causes.
Follow the recommendations provided.
No power to the LCP
Check the LCP cable for proper connection
or damage.
Replace the faulty LCP or connection cable.
Shortcut on control voltage
(terminal 12 or 50) or at control
terminals
Check the 24 V control voltage supply for
terminals 12/13 to 20-39 or 10 V supply for
terminals 50 to 55.
Wire the terminals properly.
Incompatible LCP (LCP from
VLT
®
2800 or 5000/6000/8000/
FCD or FCM)
Use only LCP 101 (P/N 130B1124) or LCP
102 (P/N 130B1107).
Wrong contrast setting
Press [Status] + [
▲
]/[
▼
] to adjust the
contrast.
Display (LCP) is defective
Test using a different LCP.
Replace the faulty LCP or connection cable.
Internal voltage supply fault or
SMPS is defective
Contact supplier.
Intermittent
display
Overloaded power supply
(SMPS) due to improper control
wiring or a fault within the
adjustable frequency drive
To rule out a problem in the control wiring,
disconnect all control wiring by removing
the terminal blocks.
If the display stays lit, then the problem is
in the control wiring. Check the wiring for
short circuits or incorrect connections. If
the display continues to cut out, follow the
procedure for display dark.
Motor not
running
Service switch open or missing
motor connection
Check if the motor is connected and the
connection is not interrupted (by a service
switch or other device).
Connect the motor and check the service
switch.
No line power with 24 V DC
option card
If the display is functioning but no output,
check that line power is applied to the
adjustable frequency drive.
Apply line power to run the unit.
LCP Stop
Check if [Off] has been pressed.
Press [Auto On] or [Hand On] (depending
on operation mode) to run the motor.
Missing start signal (Standby)
Check
5-10 Terminal 18 Digital Input
for
correct setting for terminal 18 (use default
setting).
Apply a valid start signal to start the
motor.
Motor coast signal active
(Coasting)
Check
5-12 Coast inv
. for correct setting for
terminal 27 (use default setting).
Apply 24 V on terminal 27 or program this
terminal to
No operation
.
Wrong reference signal source
Check reference signal: Local, remote or bus
reference? Preset reference active? Terminal
connection correct? Scaling of terminals
correct? Reference signal available?
Program correct settings. Check
3-13 Reference Site
. Set preset reference
active in parameter group
3-1* References
.
Check for correct wiring. Check scaling of
terminals. Check reference signal.
Motor running
in wrong
direction
Motor rotation limit
Check that
4-10 Motor Speed Direction
is
programmed correctly.
Program correct settings.
Active reversing signal
Check if a reversing command is
programmed for the terminal in parameter
group
5-1* Digital inputs
.
Deactivate reversing signal.
Wrong motor phase connection
See
chapter 5.5 Checking Motor Rotation
Maintenance, Diagnostics an...